Gas Insulated Divider
750KV/300pF SF6 Hybrid Capacitor Voltage Divider & Coupling System
This ultra-high voltage hybrid device delivers dual functionality for 800KV-class systems, combining precision measurement with power line communication capabilities in a single SF6-insulated unit with exceptional <5pC partial discharge performance.
Technical Specifications
Parameter | Specification | Engineering Benefit |
---|---|---|
Rated Voltage | 750KV | Designed for 800KV systems with 6.25% margin |
Capacitance | 300pF | Optimal balance for measurement & PLC coupling |
Frequency | 50Hz | Standard power frequency operation |
Voltage Ratio | 2000:1 | 375V output at rated voltage |
Accuracy | ≤±1% | Class 1 measurement precision |
Partial Discharge | <5pC @750KV <3pC @600KV | Superior PD performance for EHV systems |
Dielectric Loss | <0.3% | Minimal signal attenuation |
Temp Coefficient | <0.0005 | Stable across -40°C to +85°C |
Overvoltage | 825KV for 60s | 110% rated voltage withstand |
Operation Time | 15 minutes continuous | Thermally optimized duty cycle |
Dual-Role Performance
As Voltage Divider
2000:1 ratio for EHV protection systems
±1% accuracy meets metering-class requirements
Ultra-low <5pC partial discharge
As Coupling Capacitor
300pF optimized for carrier signal injection
Low-loss design maximizes PLC efficiency
Integrated solution reduces substation footprint
PD Control Technology
Quad-Shield Electrodes: Four-stage grading rings
Superfinish Surfaces: Mirror polish (Ra<0.3μm)
Gas Purity System: Active SF6 filtration
Thermal Management: 15-minute operation limit prevents gas overheating
Installation Requirements
Vibration-isolated foundation (max 0.05g)
Maintain SF6 pressure at 0.68±0.02MPa (20°C)
Measurement connections:
Triple-shielded coaxial cables
Minimum 10mm conductor diameter
Clearance distances:
6m to grounded structures
9m to other HV equipment
Maintenance Schedule
Interval | Procedure | Acceptance Criteria |
---|---|---|
Pre-operation | Gas density check | 0.66-0.70MPa |
Weekly | Surface inspection | No visible contamination |
Monthly | Partial discharge test | <5pC @750KV |
Quarterly | Capacitance verification | 300pF ±2% |
Compliance Standards
IEC 60060-1:2010 (High-voltage test techniques)
IEC 60358-1:2012 (Coupling capacitors/dividers)
IEEE C93.3-2020 (Power line carrier coupling)
GB/T 4109-2020 (Chinese HV capacitor standards)
Critical Notice: The 15-minute operation limit must be strictly observed to prevent SF6 gas decomposition. Allow 45 minutes cooling after each operation cycle.