High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

>400kV Range

LQTT 700kV(2×350kV) /250kVA AC Test Transformer

This 700kV AC series test transformer enables partial discharge detection for critical HV assets including gas-insulated switchgear (GIS), power transformers, and extra-high-voltage cables. With <5pC sensitivity certified under IEC 60270, it provides reliable insulation assessment for utilities perf···


>>>WhatsApp Communication<<<

Product Details

Product Tags

Technical Specifications (Standardized Format)

Model:2×350kV/ 250kVA
Type:Cylindrical, two-module series, single-phase
Frequency:50Hz

ParameterValueStandard
Rated CapacityLV: 250kVA, HV: 700kVAIEC 60076
Rated VoltageLV: 2×0.6kV, HV: 2×350kV
Rated CurrentLV: 2×208.3A, HV: 0.375A
No-Load Current≤10%IEC 60076-1
Waveform Distortion≤3% THDIEEE C57.12.00
Impedance Voltage≤15%
Overload Capacity125% current for 300sIEC 60076-11
Overvoltage Withstand110% U<sub>H</sub> (770kV) for 60s
Partial Discharge (PD)<5pC at 100% U<sub>H</sub>IEC 60270
Insulation Level10kV/1min (LV to earth)IEC 61180
Noise Level≤60 dB(A) @ 4mISO 3746
Voltage RatioMeasurement winding: 2000:1

Key Technical Highlights

1. Safety Protection System

  • HV terminal grounded via 5/5A current transformer (real-time monitoring & operator protection)

  • 3kV surge arresters on excitation/transfer windings (IEC 60099-4 compliant)

  • Dual grounding points on transformer housing

2. Thermal Performance

Operating ModeDurationTemperature Rise Limit
100% rated load60 minutesWinding ≤65K, Oil surface ≤55K
80% rated loadContinuousWinding ≤65K, Oil surface ≤55K

3. Oil Insulation System

  • Type 25# mineral oil (GB 2536 compliant)

  • Breakdown voltage: >60kV/2.5mm

  • Moisture content: <10ppm

  • Dielectric loss: ≤0.5% @ 90°C

  • Acetylene-free / Solidification point: ≤-40°C


Modular Design Components

▶ Upper Stage Transformer (HCTT-125kVA/350kV)

  • PD Level: <5pC at 350kV

  • Insulation Resistance: >2500MΩ (HV-LV-earth)

  • Measurement Winding Ratio: 1000:1

  • Cooling: ONAN (IEC 60076-2)

▶ Sub-Stage Transformer (HCTT-250kVA/350kV)

  • Transfer Capacity: 125kVA @ 0.6kV

  • Impedance Voltage: ≤4.5%

  • Insulation Withstand: 10kV/1min (LV-HV-housing)


>>>WhatsApp Communication<<<