>400kV Range
Core System Specifications
Parameter | Value | Standard |
---|---|---|
System Configuration | Two-stage cascade (HCTT 500kV ×2) | Cylinder type |
Rated Voltage | HV Output: 1000kV LV Input: 2×3kV | IEC 60060-1 |
Rated Current | HV: 0.5A LV: 2×83.3A | IEEE C57.12.00 |
Partial Discharge | <5pC @ 1000kV <2pC @ 800kV | IEC 60270 Class II |
Waveform Distortion | ≤3% | IEEE 432 |
Noise Level | ≤65dB @ 4m (full load) | ISO 3746 |
Stage-Wise Technical Breakdown
1. Upper Stage Transformer (HCTT 250kVA/500kV)
- **Thermal Resilience:**
110% overvoltage (550kV/60s) without insulation failure
- **Insulation Resistance:**
>2500MΩ (HV-LV-earth)
- **Duty Cycle:** 15min ON / 15min OFF ×8 cycles daily
- **Cooling:** ONAN (Oil Natural Air Natural)
2. Lower Stage Transformer (HCTT-500kVA/500kV)
- **Measurement System:** 1000:1 ratio winding
- **Oil Specifications:**
- Dielectric loss <0.5% @ 90°C
- Acetylene-free / Solidifying point >40°C
- **Insulation Tests:**
10kV/1min (LV-HV-shell)
Certified Safety & Protection
Grounding System:
HV terminal earthed via 5/5A CT for real-time monitoringSurge Protection:
3kV arresters on excitation & transfer windingsThermal Limits:
Winding ΔT: <65K
Oil surface ΔT: <55K
Overload Capacity:
125% current (0.625A) for 300s
Compliance Framework
- **Partial Discharge:** IEC 60270 Class II
- **Insulation Coordination:** IEC 60071-1
- **Safety:** IEC 61010-1 Cat IV
- **Oil Testing:** ASTM D877 / IEC 60156
Operational Advantages
Precision Control:
≤±5% voltage deviation in cascade modeRugged Construction:
IP67-rated insulated barrel designMaintenance Features:
Oil injection/release valves + dielectric monitoring
Technical FAQs (Snippet-Optimized)
Q: What’s the maximum daily operational duration at 1000kV?
A: 2 hours total (8×15min cycles with 15min cooling intervals).
Q: Is this system suitable for HVDC component testing?
A: No – use dedicated DC test sets for capacitors/HVDC applications.
Q: Oil replacement criteria?
*A: When dielectric strength drops below 30kV/mm (per IEC 60296).*