LQTT 1000kV/500kVA HV Test Transformer | IEC-Compliant Cascade System for Dielectric Testing

500kVA single-phase cascaded AC test transformers for 1000kV dielectric tests. Features <2pC partial discharge, ONAN cooling, and dual-stage voltage regulation. Compliant with IEC 60270 for utility-scale insulation testing.


>>>WhatsApp Communication<<<

Product Details

Product Tags

Core System Specifications

ParameterValueStandard
System ConfigurationTwo-stage cascade (HCTT 500kV ×2)Cylinder type
Rated VoltageHV Output: 1000kV
LV Input: 2×3kV
IEC 60060-1
Rated CurrentHV: 0.5A
LV: 2×83.3A
IEEE C57.12.00
Partial Discharge<5pC @ 1000kV
<2pC @ 800kV
IEC 60270 Class II
Waveform Distortion≤3%IEEE 432
Noise Level≤65dB @ 4m (full load)ISO 3746

Stage-Wise Technical Breakdown

1. Upper Stage Transformer (HCTT 250kVA/500kV)

- **Thermal Resilience:**  
  110% overvoltage (550kV/60s) without insulation failure  
- **Insulation Resistance:**  
  >2500MΩ (HV-LV-earth)  
- **Duty Cycle:** 15min ON / 15min OFF ×8 cycles daily  
- **Cooling:** ONAN (Oil Natural Air Natural)

2. Lower Stage Transformer (HCTT-500kVA/500kV)

- **Measurement System:** 1000:1 ratio winding  
- **Oil Specifications:**  
  - Dielectric loss <0.5% @ 90°C  
  - Acetylene-free / Solidifying point >40°C  
- **Insulation Tests:**  
  10kV/1min (LV-HV-shell)

Certified Safety & Protection

  • Grounding System:
    HV terminal earthed via 5/5A CT for real-time monitoring

  • Surge Protection:
    3kV arresters on excitation & transfer windings

  • Thermal Limits:

    • Winding ΔT: <65K

    • Oil surface ΔT: <55K

  • Overload Capacity:
    125% current (0.625A) for 300s


Compliance Framework

- **Partial Discharge:** IEC 60270 Class II  
- **Insulation Coordination:** IEC 60071-1  
- **Safety:** IEC 61010-1 Cat IV  
- **Oil Testing:** ASTM D877 / IEC 60156

Operational Advantages

  • Precision Control:
    ≤±5% voltage deviation in cascade mode

  • Rugged Construction:
    IP67-rated insulated barrel design

  • Maintenance Features:
    Oil injection/release valves + dielectric monitoring


Technical FAQs (Snippet-Optimized)

Q: What’s the maximum daily operational duration at 1000kV?
A: 2 hours total (8×15min cycles with 15min cooling intervals).

Q: Is this system suitable for HVDC component testing?
A: No – use dedicated DC test sets for capacitors/HVDC applications.

Q: Oil replacement criteria?
*A: When dielectric strength drops below 30kV/mm (per IEC 60296).*