>400kV Range
Core Technical Specifications
1. Main Transformer (Upper Stage)
Parameter | Value | Standard |
---|---|---|
Model | LQTT 1000kV/200kVA | Cylinder type |
Rated Voltage | HV Winding: 1000kV Excitation: 2×0.6kV | IEC 60060-1 |
Rated Current | HV: 0.2A Excitation: 2×166.7A | - |
Waveform Distortion | ≤3% | IEEE 432 |
Partial Discharge (PD) | <5pC @ 1000kV <3pC @ 800kV | IEC 60270 |
Impedance Voltage | ≤15% | - |
2. Cascaded Transformers
(a) Upper Stage: HCTT 100kVA/500kV
Dimensions: Ø1290/1410×3560mm
Weight: 7,000 kg
Overload Capacity: 150% current for 300s
(b) Lower Stage: HCTT 200kVA/500kV
Measurement Ratio: 1000:1
Insulation: Fixed cylinder design
Critical Safety & Performance Features
Grounding Protection:
HV terminal earthed via 5/5A CT for real-time current monitoring & operator safety.Thermal Resilience:
Continuous operation @ 80% load (ΔT winding <65K, oil <55K)
110% overvoltage (1100kV/60s) without insulation failure
Environmental Compliance:
Noise: ≤60dB (measured at 4m)
Oil Maintenance: Injection/release valves standard
Certifications & Standards
- **Dielectric Safety:** IEC 61010-1 Cat IV
- **Test Accuracy:** ±0.5% (calibrated per IEC 62586-2)
- **Partial Discharge:** IEC 60270 Class II
- **Environmental:** IP67 (substation-grade ingress protection)
Application Scenarios (Keyword-Rich)
Energy Sector:
Insulation integrity tests for 500kV+ substations
Transformer acceptance testing (per ANSI/NETA ATS)
Manufacturing:
Dielectric strength validation of GIS components
Renewables:
Cable fault location in offshore wind farms
FAQ Section (Optimized for Featured Snippets)
Q: What’s the calibration interval for this HV test system?
*A: Annual traceable calibration required (IEC 62586-2), with quarterly field verification.*
Q: Can it test HVDC equipment?
A: No – dedicated DC test sets are needed for capacitor banks/HVDC applications.
Q: Maximum continuous operating time at full load?
*A: 60 minutes @ 1000kV/0.2A (ambient start temp ≤40°C).*