High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

>400kV Range

LQTT 1000kV/1000kVA HV Test Transformer | IEC 60270-Compliant Cascade System

1000kVA single-phase cascaded AC test transformers for ultra-high-voltage dielectric testing. Features <2pC partial discharge, ONAN cooling, and 120% overload capacity. Certified to IEC 60060-1 for utility-scale insulation validation.


>>>WhatsApp Communication<<<

Product Details

Product Tags

Core System Specifications

ParameterValueStandard
System ConfigurationTwo-stage cascade (HCTT 500kV ×2)Cylinder type
Rated VoltageHV Output: 1000kV
LV Input: 2×3kV
IEC 60060-1
Rated CurrentHV: 1A
LV: 2×166.6A
IEEE C57.12.00
Partial Discharge<5pC @ 1000kV
<2pC @ 700kV
IEC 60270 Class II
Waveform Distortion≤3% (System)IEEE 432
Dielectric Loss<0.5% @ 20°CIEC 60247
Noise Level≤65dB(A) @ 4mISO 3746

Stage-Wise Technical Breakdown

1. Upper Stage Transformer (HCTT-500kVA/500kV)

- **Thermal Resilience:**  
  110% overvoltage (550kV/60s) without damage  
- **Insulation Resistance:**  
  >2500MΩ (HV-LV-earth)  
- **Duty Cycle:** 1hr ON / 1hr OFF ×8 cycles daily  
- **Cooling:** ONAN (Oil Natural Air Natural)  
- **Overload:** 120% current (1.2A) for 300s

2. Lower Stage Transformer (HCTT-500kVA/500kV)

- **Measurement System:** Dedicated measurement winding  
- **Oil Specifications:**  
  - Dielectric loss <0.5% @ 20°C  
  - Acetylene-free  
- **Insulation Tests:**  
  10kV/1min (LV-HV-shell)  
- **Critical Protection:**  
  Integrated 5/5A CT for HV grounding

Certified Safety & Performance

  • Thermal Management:

    • Winding ΔT: <65K

    • Oil surface ΔT: <55K

  • Voltage Stability:
    ≤5% deviation in cascade mode

  • Protection Systems:

    • Surge arresters on all excitation windings

    • Dual-stage oil injection/release valves

  • Environmental Resilience:
    ONAN cooling for continuous 8-cycle operation


Compliance Framework

- **Partial Discharge:** IEC 60270 Class II  
- **Insulation Coordination:** IEC 60071-1  
- **Safety:** IEC 61010-1 Cat IV  
- **Noise Emission:** ISO 3746:2010  
- **Dielectric Testing:** ASTM D877

Operational Advantages

  • Extended Duty Cycle:
    8×1hr full-load operations daily

  • Precision Metrics:
    ≤4.5% waveform distortion (per stage)

  • Diagnostic Capabilities:
    PD monitoring down to 2pC at 700kV

  • Robust Construction:
    Industrial-grade cylinder design


Technical FAQs (Snippet-Optimized)

Q: Maximum daily operational duration at 1000kV?
A: 8 hours total (8×1hr cycles with 1hr cooling intervals).

Q: Calibration requirements for PD measurement?
*A: Semi-annual calibration per IEC 60270 using pulse injection method.*

Q: Ambient temperature limitations?
*A: Rated for -25°C to +45°C operation (IEC 60076-11).*


>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<