>400kV Range
LQTT Series | 500kV / 1000kVA AC Withstand Voltage Test Transformer
Single-Phase, Cylindrical Design
Key Specifications
Rated Capacity: 1,000 kVA
Frequency Range: 50 Hz, 60 Hz, 100 Hz, 120 Hz
Rated Voltage:
High Voltage (HV): 500 kV
Low Voltage (LV): 4 × 3 kV (configurable windings)
Rated Current:
HV Side: 2 A
LV Side: 4 × 83.3 A
Flexible Winding Configurations
The LV windings support series/parallel connections for adjustable HV output:
All 4 Windings in Series:
→ Output: 125 kV at 2 ATwo Series + Two Parallel Groups:
→ Output: 250 kV at 2 AAll 4 Windings in Parallel:
→ Output: 500 kV at 2 A
Safety & Monitoring
HV terminal grounded via 5/5A current transformer (CT).
Real-time HV current monitoring during tests ensures operator safety and system integrity.