200kV ~ 400kV Range
LQHVF 350kV/6000pF Ultra-Low PD Voltage Divider
High-capacitance divider with ≤2pC partial discharge at 350kV, 2000:1 ratio, and reactor-synchronized operation for precision HV testing
Technical Specifications
Parameter | Specification | Testing Standard |
---|---|---|
Rated Voltage | 350kV AC (50Hz) | IEC 60060-1 |
Nominal Capacitance | 6000pF ±3% | IEC 60358 |
Dividing Ratio | 2000:1 | - |
Dielectric Loss (tanδ) | <0.2% | IEC 60247 |
Partial Discharge (PD) | ≤2pC @ 350kV | IEC 60270 |
Measuring Accuracy | ≤±1% | IEC 60060-2 |
Continuous Operation | 60 min @ rated voltage/current | IEC 61180 |
Insulation Withstand | 385kV for 1 minute (no discharge) | IEC 60060-1 |
Cooling System | ONAN (Oil Natural Air Natural) | IEC 60296 |
Reactor Synchronization | Operating time matches reactor capabilities | IEC 60289 |
Advanced Design Features
Ultra-Low PD Construction
Industry-leading discharge control:
≤2pC at 350kV (IEC 60270 Class I)
Triple-shielded electrode design
Electro-polished surfaces (Ra <0.5μm)
Vacuum-processed dielectric oil
Reactor-Synchronized Operation
Optimized for HV reactor testing:
Continuous operation matches reactor duty cycle
Thermal stability: ΔT <3°C during operation
ONAN cooling compatibility
Harmonic distortion tolerance
Transport-Optimized System
Field-deployable modular design:
Removable aluminum corona rings
Quick-release stabilizing pedestal
Component-based packaging
30-minute assembly time
Measurement Capabilities
Scalable Connection System
Single-Stage Configuration
Direct measurement up to 350kV
Special shielded lead-wire system
Accuracy: ≤±1%
Two-Stage Serial Connection
Extended voltage measurement range
Phase-synchronized outputs
Corona-free HV terminals
Variable Frequency Compatibility
Operates with VLF (0.1Hz) to 150Hz power sources for:
Cable testing applications
Dielectric spectroscopy
Transformer diagnostic testing
Performance Validation
Certified Testing Protocol
Partial discharge ≤2pC verified at 350kV (IEC 60270)
Dielectric loss <0.2% at 50Hz (IEC 60247)
385kV/1min insulation withstand with zero discharge
Thermal cycling test (-30°C to +55°C)
60-minute continuous operation at 350kV
IEC 60270 IEC 60060-1 IEC 60060-2 IEC 61180
Industrial Applications
Reactor Testing
Synchronized operation for:
Shunt reactor diagnostics
Series reactor commissioning
Filter reactor harmonic analysis
High-Energy Labs
Precision measurement for:
Pulsed power systems
Plasma research facilities
Dielectric material studies
Field Commissioning
On-site HV system verification:
Substation reactor commissioning
HVDC converter station testing
Renewable energy installations