200kV ~ 400kV Range
LQHVF 350kV/1000pF Dual-Frequency Voltage Divider
Advanced capacitive divider with dual-frequency operation (50Hz/150Hz), scalable corona-free connections, and<5pc partial="" discharge="" for="" precision="" hv="" testing="">
Technical Specifications
Parameter | Specification | Testing Standard |
---|---|---|
Rated Voltage | 350kV AC | IEC 60060-1 |
Nominal Capacitance | 1000pF ±3% | IEC 60358 |
Frequency Range | 50Hz (Rated) / 150Hz (Operating) | IEC 60060-1 |
Dielectric Loss (tanδ) | <0.3% | IEC 60247 |
Partial Discharge | <5pC @ 350kV <2pC @ 210kV | IEC 60270 |
Measuring Accuracy | ≤±1% | IEC 60060-2 |
Insulation Withstand | 385kV for 1 minute (no discharge) | IEC 60060-1 |
Continuous Operation | 60 minutes @ 100% rated voltage | IEC 61180 |
Cooling System | ONAN (Oil Natural Air Natural) | IEC 60296 |
Advanced Design Features
Dual-Frequency Operation
Precision measurement at 50Hz and 150Hz:
Variable frequency power source compatibility
Stable ratio accuracy across frequencies
Phase displacement <0.1°
Scalable HV Connections
Flexible measurement configurations:
Corona-free HV terminals
Single-stage and two-stage serial measurement
Special shielded lead-wire system
Transport-Optimized Design
Field-deployable components:
Removable aluminum corona rings
Stabilizing pedestal with quick-release
Modular assembly (30 min setup)
Performance Validation
Certified Testing Protocol
Partial discharge <2pC @ 60% rated voltage (210kV)
Dielectric loss <0.3% at 50Hz and 150Hz
Insulation withstand: 385kV/1min (110% rated) with zero discharge
Thermal stability: <3°C temperature rise during 60-min operation
Frequency response variation <0.2% (50-150Hz)
IEC 60270 IEC 60060-1/2 IEC 61869-11 ISO/IEC 17025
Measurement Capabilities
Multi-Stage Connection System
Single-Stage Configuration
Direct HV measurement up to 350kV
Special lead-wire to variable frequency source
Accuracy: ≤±1%
Two-Stage Serial Connection
Extended voltage measurement capability
Scalable corona-free connections
Phase-synchronized measurement
HV Connection: Corona-free design with shielded connectors prevents surface discharge during measurement
Industrial Applications
Frequency-Variable Testing
VLF (Very Low Frequency) applications:
Cable withstand testing (0.1Hz - 0.01Hz)
Transformer diagnostic testing
Rotating machine insulation testing
High-Power Laboratories
Precision measurement for:
Impulse voltage waveform analysis
Partial discharge localization
Dielectric response testing
Field Testing
Transportable HV measurement:
Substation equipment diagnostics
Renewable energy farm commissioning
On-site calibration of HV systems