200kV ~ 400kV Range
LQHVF 300kV/300pF Dual-Function Capacitor: Ultra-High-Ratio Precision Instrument
Dual-Role Solution for Critical High-Voltage Systems
The LQHVF 300kV/300pF redefines precision measurement with its industry-leading 3000:1 voltage ratio and dual-function capability. Engineered for EHV transmission systems and research facilities, this solution delivers:
Ultra-high 3000:1 ratio for microvolt-level resolution
Dual functionality: Precision voltage measurement + signal coupling
Ultra-low partial discharge: <5pC @300kV
Laboratory-grade accuracy (≤±1%)
Breakthrough Measurement Resolution
With 3000:1 ratio, 300kV measurements resolve to 100V - enabling detection of sub-millisecond transients and micro-discharges imperceptible to standard dividers.
Technical Specifications
Parameter | Specification | Performance Advantage |
---|---|---|
Rated Voltage | 300kV | EHV transmission system compatibility |
Nominal Capacitance | 300pF | Optimized for high-resolution measurement |
Voltage Ratio | 3000:1 | Industry's highest precision ratio |
Accuracy | ≤±1% | Exceeds IEC 60060-2 Class 0.5 |
Partial Discharge | <5pC @300kV | Ultra-clean signal transmission |
Dielectric Loss | <0.5% | Superior insulation integrity |
Operating Time | 60 minutes @300kV | Extended testing capability |
Cooling System | ONAN | Maintenance-free thermal management |
Dual-Function Capabilities
As Precision Voltage Divider
3000:1 ratio with ≤±1% error enables:
Calibration of protection relays
Transient overvoltage analysis
Partial discharge localization
Harmonic distortion measurement
As Coupling Capacitor
300pF capacitance optimized for:
Secure protection signaling
Power line carrier (PLC) communication
SCADA data transmission
Fault recording synchronization
Precision Design Features
Oil-Immersed Capacitors
High-purity mineral oil provides stable dielectric properties at 300kV.
Removable Corona Rings
Aerospace-grade aluminum alloy prevents discharge at 300kV+.
Modular Arm System
Separable LV/HV arms enable reconfiguration and maintenance.
Stabilized Removable Base
Engineered pedestal with seismic-grade stability.
Ultra-High-Ratio Applications
Research & Development
Nanosecond transient capture in high-energy physics experiments and plasma research.
Protection System Calibration
Precision verification of 300kV+ protective relays with 0.1% resolution.
Partial Discharge Mapping
Localization of micro-discharges in power transformers and GIS systems.
Operational Advantages
Unmatched Resolution: 100V equivalent at 300kV
Dual-Function Efficiency: Single device replaces two systems
Ultra-Low Noise:
<5pc pd="" ensures="" signal="" integrity="">
Thermal Stability: ONAN cooling maintains accuracy
"The 3000:1 ratio revealed transients previously undetectable in our 500kV test bed - revolutionizing our research capabilities."
- Director, High-Energy Research Facility
Installation & Operation Protocol
Site Preparation: Level surface with 5m clearance
Assembly: Secure corona rings using alignment markers
Grounding: Dual 35mm² cables to station grid
Configuration:
Voltage measurement: Connect to test set
Coupling function: Terminate to PLC transmitter
Pre-Test: Verify PD levels at 240kV
Operation: Max 60 minutes continuous at 300kV
Safety: Maintain 6m clearance during operation
Compliance & Standards
Certified to international standards:
IEC 60358-1: Coupling capacitors & capacitor dividers
IEEE C57.13: Instrument transformer requirements
IEC 60060-1: High-voltage test techniques
IEC 60270: Partial discharge measurements