200kV ~ 400kV Range
LQHVF 300kV/2000pF Capacitive Voltage Divider: Extended-Duty Precision Instrument
High-Resolution Measurement for Demanding Applications
The LQHVF 300kV/2000pF sets new standards in high-voltage precision with its exceptional 3500:1 ratio and extended-duty operation capability. Engineered for critical power system testing and calibration laboratories, this solution delivers:
Ultra-high 3500:1 ratio for 85.7V equivalent at 300kV
Continuous operation at 225kV (75% rated voltage)
Ultra-low dielectric loss (
<0.2%) 20="" at="">330kV insulation withstand (110% rated voltage)
Extended Duty Operation
Unlimited operation at 225kV combined with 1-hour rating at 300kV provides unmatched flexibility for long-duration tests.
Technical Specifications
Parameter | Specification | Performance Advantage |
---|---|---|
Rated Voltage | 300kV | Ultra-high voltage system testing |
Rated Capacitance | 2000pF | Optimal for precision measurements |
Low Voltage Ratio | 3500:1 | Highest resolution in class |
Accuracy | ≤±1% | Exceeds IEC 60060-2 Class 0.5 |
Dielectric Loss | <0.2% @20°C | Industry-leading insulation quality |
Insulation Level | 330kV/60s | 110% rated voltage withstand |
Cooling System | ONAN | Passive thermal management |
100%
300kV operation
60 minutes maximum
75%
225kV operation
Continuous duty
50Hz
→
300Hz
Precision Design Features
Ultra-Low Loss Capacitors
Special dielectric formulation achieves<0.2% 20="" loss="" at="">
Removable Corona Rings
Aerospace-grade aluminum alloy rings prevent discharge at 300kV+.
Stabilized Removable Base
Engineered pedestal with seismic restraints and vibration damping.
Scalable HV Connection
Corona-free connectors for single (300kV) or series (600kV) configurations.
Extended Duty Performance
Continuous Operation Capability
Maintains ≤±1% accuracy during unlimited operation at 225kV (75% rated voltage) - ideal for long-duration tests like:
72-hour transformer temperature rise tests
Extended cable aging studies
Continuous power quality monitoring
High-Resolution Measurement
3500:1 ratio delivers 85.7V equivalent at 300kV - enabling detection of micro-discharges and nanosecond transients.
Industry Applications
Calibration Laboratories
Reference standard for calibrating 300kV+ measurement systems with NIST-traceable accuracy.
Transformer Manufacturing
Extended induced voltage tests on 500kV transformers with continuous monitoring.
Research Facilities
Long-duration dielectric studies and material aging research at controlled voltages.
Operational Advantages
Unmatched Resolution: 3500:1 ratio enables new measurement capabilities
Extended Operation: Unlimited runtime at 225kV reduces test interruptions
Thermal Stability: ≤0.05% ratio drift during voltage transitions
Frequency Flexibility: Consistent accuracy from 50-300Hz
"The continuous operation at 225kV allowed us to complete 72-hour transformer tests without interruption - eliminating measurement gaps that previously affected our data accuracy."
- Chief Engineer, Power Transformer Facility
Installation & Operation Protocol
Site Preparation: Level surface with 6m clearance
Assembly: Secure corona rings using alignment markers
Grounding: Dual 35mm² cables to independent ground
Configuration:
Select single-stage (300kV) or series (600kV)
Connect via special lead-wire to VF source
Voltage Selection:
300kV: Max 60 minutes continuous
225kV: Unlimited operation
Safety: Maintain 7m clearance during 330kV tests
Compliance & Standards
Certified to highest precision standards:
IEC 60060-1/2: High-voltage test techniques
IEEE 4: Standard for HV testing
ISO/IEC 17025: Testing laboratory competence
ASTM D150: Standard test methods for AC loss
Includes NIST-traceable calibration certificate.