High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

200kV ~ 400kV Range

Ultra-Low PD 250kV/200pF Capacitor Voltage Divider & Coupling Capacitor | LQHVF Series

250kV/200pF dual-function capacitor with <2pC partial discharge, ≤1% accuracy, and ONAN cooling. Certified 1000:1 ratio for precision high-voltage measurement and power line communication applications.


  • US$ 5,544.00
  • Lead time: 30days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHVF 250kV/200pF Capacitor Voltage Divider & Coupling Capacitor: Industry-Leading Ultra-Low PD Solution

Precision Dual-Function Instrument for Critical HV Systems

The LQHVF 250kV/200pF sets new standards in high-voltage measurement with unprecedented partial discharge performance (<2pC @250kV). This dual-function instrument combines precision voltage division and power line coupling capabilities in a single oil-immersed package, delivering:

  • Laboratory-grade accuracy (≤1%) in field conditions

  • Ultra-clean signal coupling for protection relays

  • 60-minute continuous operation at full rated voltage

  • Modular design for rapid deployment

Breakthrough PD Performance

With PD levels below 2pC at 250kV - 60% lower than industry standards - enabling sensitive measurements in noisy substation environments per IEC 60270 Class II requirements.

Technical Specifications

ParameterSpecificationPerformance Advantage
Rated Voltage250kVEHV transmission system compatibility
Accuracy≤ ±1%Exceeds IEC 60060-2 Class 0.5 requirements
Partial Discharge<2pC @100% UnIndustry's lowest noise floor for sensitive measurements
Dielectric Loss<0.5%Superior insulation integrity
Continuous Operation60 minutes @250kVExtended testing without derating
Cooling SystemONAN (Oil Natural Air Natural)Zero-maintenance thermal management

Patented Modular Design

Oil-Immersed Capacitors

High-purity mineral oil provides superior dielectric strength and thermal conductivity at 250kV.

Quick-Disconnect Corona Rings

Tool-free aluminum alloy rings eliminate corona above 150kV, detachable in<90 seconds.="">

Interchangeable Arm System

Standardized HV/LV arm connections enable reconfiguration for different voltage classes.

Portable Base

Removable pedestal with forklift channels and seismic restraints for field deployment.

Dual-Function Applications

As Precision Voltage Divider

1000:1 ratio with ≤1% error for:

  • Calibration of 220kV+ protection relays

  • Dielectric response testing of transformers

  • Harmonic analysis at 50Hz fundamental frequency

As Coupling Capacitor

200pF capacitance optimized for:

  • Power line carrier (PLC) communication

  • Directional comparison protection signaling

  • Transient fault recording

Operational Advantages

  • Zero PD Interference:

    <2pc noise="" enables="" sensitive="" pd="" measurements="">
  • 60-Minute Thermal Stability: ONAN cooling maintains ±0.1% accuracy during extended tests

  • Test-Ready Design: Pre-installed PD monitoring terminals

  • Rapid Deployment: Field assembly in

    <30 minutes="">

The lt 2pC PD performance allows us to detect incipient insulation faults previously masked by measurement noise - a game-changer for predictive maintenance.
               - Chief Engineer, High-Voltage Laboratory

Installation & Safety Protocol

  1. Site Preparation: Level concrete pad (min. 2m x 2m)

  2. Grounding: Dual 35mm² copper cables to station grid

  3. Corona Ring Assembly: Hand-tighten until alignment marks match

  4. Pre-Energization Check: Verify oil level in sight glass

  5. Operational Limit: Max 60 continuous minutes at 250kV

  6. Decommissioning: 30-minute discharge cycle before disassembly

Compliance & Certifications

Third-party verified to international standards:

  • IEC 60358-1: Coupling capacitors and capacitor dividers

  • IEC 60270: Partial discharge measurements

  • IEEE C57.13: Requirements for instrument transformers

  • EN 60076: Power transformers

KEMA-certified test reports available for all production units.