Relay Tester/Secondary Circuit Tester
LQMG2000E Digital Clamp Phase Meter
Advanced Non-Contact Phase Measurement
Engineered for field technicians, the LQMG2000E delivers precision phase analysis (0-360°) with dual insulated clamps for current measurement from 0.1mA to 10A and voltage testing up to 500V - all without circuit interruption.
Product Parameters
Reference to working conditions
Environment temperature | (23±5)℃ |
Environmental humidity | (45~75)% RH |
Measured signal waveform | Sine wave、β=0.02 |
Measured signal frequency | (50±0.2)Hz |
The position of the measured current- carrying conductor at the clamp mouth | any |
The amplitude of The measured signal when measuring The phase | 100~220V、0.5~1.5A |
External reference frequency electromagnetic field interference | Should be avoided |
Measurement error of AC voltage
Limit of quantity | Resolution | Basic error limit |
20V | 0.01V | ±(0.3% reading +0.2% range) |
200V | 0.1V | |
500V | 1V |
Measurement error of ac current
Limit of quantity | Resolution | Basic error limit |
200mA | 0.1mA | ±(0.3% reading +0.2% range) |
2A | 1mA | |
10A | 10mA |
Voltage input circuit impedance when u1-u2 phase is measured:40KΩ
Range | Resolution | Basic error limit |
0~360° | 1° | ±2° |
Rated working condition
Environment temperature | (0~40)℃ | |
Environmental humidity | (20~80)% RH | |
Measured signal waveform | Sine wave、β=0.05 | |
Measured signal frequency | (50±0.5)Hz | |
The position of the measured current- carrying conductor at the clamp mouth | any | |
The amplitude of The measured signal when measuring The phase | U1-U2 phase: 30V ~ 500V | |
I1-I2 phase: 10mA ~ 10.00A | ||
U1-I2 phase or I1-U2 phase: 10V ~ 500V, 10mA ~ 10.00A | ||
External reference frequency electromagnetic field interference | Should be avoided | |
Limit of rated operating error | Under the above rated working conditions, the rated working error limit of each measured shall not exceed twice the corresponding basic error limit |
Other technical features
Display digit | Three and a half | |
Sampling rate | 3 times per second | |
The power supply | Single 9V laminated battery, The power supply current is less than 5mA | |
Overall dimensions | Case size | 192×95×55mm3 |
Clamp shell size | 140×42×20mm3 | |
Jaw size | Φ7mm×9mm | |
Weight | Body | 280g |
Test forceps | 2×200g | |
Storage conditions | The temperature | -10℃~50℃ |
Key Specifications
Current Range: 0.1mA-10A (AC)
Voltage Range: 3V-500V (AC)
Phase Accuracy: ±1°
Display: 25mm high-contrast LCD (70° tilt)
Power: Low-consumption design with battery check
Core Testing Capabilities
1. Comprehensive Electrical Analysis
U-U, I-I, U-I phase relationships
Three-phase sequence detection
Transformer wiring verification
2. Precision Clamp Technology
Patent-pending current sensors
0.1mA resolution for sensitive circuits
Fully insulated (1000V rated)
3. Enhanced Field Operation
Single-handed operation
70° adjustable display
Rubberized shockproof casing
User-Centric Design
Intuitive Interface
Rotary switch for quick measurement selection
Battery Efficiency
Micro-power circuit with voltage monitoring
Safety Built-In
500V input protection
Safety Compliance
1000V insulation between clamps/chassis
Double-insulated probe inputs
IP54 rated enclosure
Why Professionals Prefer LQMG2000E
Ultra-Sensitive - Measures down to 0.1mA current
Non-Invasive - No circuit disconnection required
All-Angle Visibility - 70° adjustable display