Relay Tester/Secondary Circuit Tester
LQHV-105A Intelligent CT/PT Field Test System
Complete transformer verification in one compact unit with automatic curve generation and instant field reporting
Product Parameters
Function Table
| I. Current Transformer (CT) | II. Voltage Transformer (PT) |
| 1. Magnetization Curve | 1. Excitation Characteristic Test |
| 2. Transformation Ratio Test | 2. Transformation Ratio Test |
| 3. Polarity | 3. Polarity |
| 4. 5% and 10% error curve | 4. Withstand Test of Power Frequency |
| 5. Current Injecting | 5. Resistance Test |
| 6. FAST TEST | 6. Calculation of Knee Point Value |
| 7. Withstand Test of Power Frequency Alternating Current | 7. Actual Secondary Load Test |
| 8. Automatic Calculation of Excitation Knee Point Value | |
| 9. Actual Secondary Load Test | |
| 10. Resistance Test |
Technical Parameter Table
| Major Technical Parameters | |
| Operational Power Supply | AC220V±20V, 50~60Hz |
| Equipment Power Supply Output Waveform | Sine Wave |
| Single Machine Output Voltage of Excitation Characteristic | 0~1200V |
| Excitation Current Set | 0~20A |
| Single Machine Output Current of Transformation Ratio Test | 0~1000A |
| CT ratio measurement range | 5~25000A/5A(5000A/1A) |
| PT ratio measurement range | 1~500KV |
| Load Range | 5~500VA |
| Resistance measurement range | 0.1~300Ω |
| Error | ≤0.5%(0.3%*Reading+0.2%*Range) |
| Operating Temperature | -10℃~+40℃ |
| Relative Humidity | <90RH% |
| Altitude | ≤1000m |
| Overall Dimension(Length*Width*Height) | 450*350*350(mm) |
| Weight | ≤28Kg |
Core Testing Capabilities
Excitation Testing
0-250V/0-20A range
±0.5% accuracy
Ratio Verification
1-5000:1 range
±0.2% accuracy
Error Analysis
Automatic 5%/10% curves
Knee-point detection
Key Advantages
All-in-One Testing
Complete CT/PT verification without additional equipment
Smart Automation
Automatic inflection point detection and curve generation
Field-Ready Design
Integrated printer + USB data export (≤22kg portable unit)
Regulatory Compliance
Meets GB 20840.2-2014 & GB 20840.3-2013 standards
Simplified Testing Process
Connect test leads (auto-recognition)
Select test parameters via touchscreen
Initiate automated test sequence
Review results on-screen or print instantly
Export detailed reports via USB
Standards Compliance
GB 20840.2-2014 (Voltage Transformers)
GB 20840.3-2013 (Current Transformers)
IEC 61869-1:2007
DL/T 726-2013 (Chinese Power Standard)
Industry Applications
Utility Maintenance
Protection relay CT verification
Energy Metering
Revenue-grade PT accuracy testing
Manufacturing QC
Production line transformer testing