High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Charging Transformer

HCTT-240kV/0.25A Ultra-Low PD Charging Transformer | 60kVA HV Test System

60kVA HCTT-240kV/0.25A charging transformer features ≤5pC partial discharge level and 150% over-current capacity for precision high-voltage testing applications.


  • US$1.00; Negotiated Price
  • Lead time: 60days

>>>WhatsApp Communication<<<

Product Details

Product Tags

HCTT-240kV/0.25A Ultra-Low Partial Discharge Transformer

Product Overview

Designed for sensitive high-voltage measurements, the HCTT-240kV/0.25A delivers exceptional 60kVA performance with industry-leading ≤5pC partial discharge levels at rated voltage, making it ideal for partial discharge testing systems.

Technical Specifications

Electrical Parameters
Rated Capacity60kVA (±2%)
Input Voltage400V 3-phase ±5% (Exciting Winding)
Output Voltage240kV DC/AC (HV Winding)
Current Ratings150A (Input) / 0.25A (Output)
Frequency50Hz ±0.2% (60Hz available)
Measurement Accuracy±0.15% via 1000:1 ratio winding

Performance Highlights

Critical Parameters

  • Partial Discharge: ≤5pC @ 240kV, ≤3pC @ 192kV

  • No-load Loss: <10% of rated current

  • Waveform Purity: ≤5% THD under load

  • Dielectric Loss: <0.4% @ rated voltage

Enhanced Capabilities

FeatureSpecification
Over-current150% (0.375A) for 5 minutes
Over-voltage264kV (110%) for 60 seconds
Continuous Operation192kV/0.2A (80%) 24/7
Full Load Duration240kV/0.25A for 60 minutes

Partial Discharge Control

  • Triple-shielded winding design

  • Corona-free HV bushing with silicone grading rings

  • Ultra-clean mineral oil (≤0.1% moisture)

  • All metallic parts rounded (R5 minimum radius)

Thermal Management

  • Winding ΔT: ≤65K at full load

  • Oil ΔT: ≤55K under maximum load

  • Dual cooling circuits (natural convection + forced oil)

  • Integrated oil purifier with 5μm filtration

Insulation System

ComponentWithstand Voltage
LV Winding-Ground3kV/1min
HV Winding-Ground3kV/1min
Inter-winding3× rated voltage

Structural Design

  • Monocoque tank construction (10mm steel)

  • Vibration-damped core mounting (3Hz cutoff)

  • Modular HV terminal (upgradeable to 300kV)

  • Particle-free assembly environment (Class 1000)

Standards Compliance

  • IEC 60270 (Partial Discharge Measurements)

  • IEEE C57.129 (PD Test Procedures)

  • EN 60076-14 (Design for Low PD)

  • ASTM D1816 (Dielectric Breakdown)

Specialized Applications

  • Partial discharge calibration systems

  • HV cable qualification testing

  • Power transformer PD measurement

  • Ultra-high voltage research

  • Medical accelerator power supplies

With its exceptional ≤5pC partial discharge performance and 0.25A output current, the HCTT-240kV transformer sets new standards for precision in high-voltage test applications. The ultra-clean design ensures reliable measurements even in sensitive partial discharge detection systems.

>>>WhatsApp Communication<<<