High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Charging Transformer

HCTT-200kV/0.2A Industrial Charging Transformer | 40kVA High Voltage Power Supply

40kVA HCTT-200kV/0.2A industrial charging transformer features 125% over-current capacity and continuous 160kV operation for demanding high-voltage test applications.


  • US$1.00; Negotiated Price
  • Lead time: 60days

>>>WhatsApp Communication<<<

Product Details

Product Tags

HCTT-200kV/0.2A Industrial Charging Transformer

Product Overview

Designed for industrial high-voltage testing, the HCTT-200kV/0.2A delivers stable 200kV output with exceptional 125% over-current capacity and 1-hour continuous full-load operation capability.

Technical Specifications

Electrical Parameters
Rated Capacity40kVA (±3%)
Input Voltage400V 3-phase ±10% (Exciting Winding)
Output Voltage200kV DC/AC (HV Winding)
Current Ratings100A (Input) / 0.2A (Output)
Frequency50Hz ±0.5% (60Hz optional)
Measurement Precision±0.25% via 1000:1 ratio winding

Performance Characteristics

Core Performance

  • No-load Loss: <10% of rated current

  • Waveform Quality: ≤5% THD at full load

  • Dielectric Strength: 220kV (110%) for 60 seconds

  • Efficiency: 94% at 80% load

Robust Design Features

ParameterSpecification
Over-current Capacity125% (0.25A) for 5 minutes
Continuous Operation160kV/0.16A (80%) indefinitely
Full Load Duration200kV/0.2A for 60 minutes
Insulation Resistance>5000MΩ @ 25°C

Thermal Performance

  • Winding Temperature Rise: ≤65K at full load

  • Oil Temperature Rise: ≤55K under maximum load

  • Designed for ambient temperatures up to 50°C

  • Integrated oil circulation pump (2.5m³/h flow rate)

Insulation System

ComponentTest Voltage
LV Winding-Ground3kV/1min
HV Winding-Ground3kV/1min
Inter-winding2.5× rated voltage

Mechanical Design

  • Modular tank design with 8mm steel walls

  • Triple-sealed HV bushing (200kV BIL)

  • Anti-vibration mounting pads (5Hz resonance frequency)

  • Integrated lifting lugs (3-ton safety factor)

Compliance & Safety

  • IEC 61378 (Converter Transformers)

  • IEEE C57.12.90 (Test Procedures)

  • EN 50588 (Industrial Applications)

  • Automatic pressure relief valve (2-bar activation)

Industrial Applications

  • Cable factory acceptance testing

  • Gas-insulated switchgear (GIS) commissioning

  • High-voltage capacitor testing

  • Industrial coating systems

  • Research facility power supplies

The HCTT-200kV/0.2A's 40kVA capacity and extended over-current capability make it particularly suitable for testing capacitive loads up to 2000pF. The precision measurement winding allows direct connection to modern digital relay test sets and SCADA systems.

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message

Leave Your Message