High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

Charging Transformer

HCTT-150kV/0.4A High Power Charging Transformer | 60kVA HV Test Solution

Technical specifications for the HCTT-150kV/0.4A high-power charging transformer featuring 60kVA capacity, 150% over-current capability, and industrial-grade thermal stability.


  • US$1.00; Negotiated Price
  • Lead time: 60days

>>>WhatsApp Communication<<<

Product Details

Product Tags

HCTT-150kV/0.4A High Power Charging Transformer

Product Overview

Designed for high-current HV testing applications, the HCTT-150kV/0.4A delivers 60kVA capacity with exceptional overload capacity (150% current rating) and precision voltage regulation for demanding industrial test environments.

Core Specifications

Rated Parameters
Rated Capacity60kVA
Input Voltage400V ±10% (Exciting Winding)
Output Voltage150kV (HV Winding)
Current Ratings150A (Input) / 0.4A (Output)
Frequency50Hz/60Hz (±2% stability)
Voltage Ratio1000:1 (Measuring Winding)

Performance Highlights

Electrical Characteristics

  • No-load Current: ≤10% of rated current

  • Waveform Distortion: ≤5% THD under full load

  • Dielectric Loss: <0.4% @ rated voltage

Robust Overload Capacity

ParameterCapability
Over-current150% rated current (0.6A) for 5 minutes
Over-voltage165kV (110% rating) for 1 minute
Continuous Operation120kV/0.32A (80% rating) indefinitely
Full Load Duration150kV/0.4A for 60 minutes

Thermal Management

  • Winding Temp Rise: <65K at full load

  • Oil Surface Temp Rise: ≤55K at full load

  • Forced oil cooling optional for high-duty cycles

Insulation System

ComponentWithstand Voltage
LV Winding-Ground3kV/1min
HV Winding-Ground3kV/1min
Inter-winding1.5× rated voltage

Mechanical Design

  • Industrial-grade steel tank with corrosion protection

  • Modular bushing design for easy maintenance

  • Integrated wheels with locking mechanism (1000kg capacity)

  • Dual-level oil sight glasses with temperature markers

Safety & Compliance

  • IEC 60076-1 (Power Transformers)

  • IEEE C57.12.90 (Test Code)

  • EN 50588 (Industrial Applications)

  • Automatic Buchholz relay for fault protection

Typical Applications

  • HV cable factory acceptance testing

  • GIS (Gas Insulated Switchgear) commissioning

  • Power transformer impulse testing

  • High-current partial discharge measurements

  • Research labs for insulation materials

With its 60kVA capacity and 0.4A output current, the HCTT-150kV transformer enables stable testing of high-capacitance loads. The 150% over-current capability makes it particularly suitable for cascade connection systems and long-duration withstand voltage tests.