Gas Insulated Divider
325KV/400pF SF6 Dual-Function Capacitor Voltage Divider
Engineered for modern smart grids, this innovative device integrates precision high-voltage measurement with power line communication capabilities in a single SF6-insulated unit, delivering exceptional 400pF coupling capacity with measurement-grade accuracy.
Key Technical Specifications
Parameter | Specification | Engineering Benefit |
---|---|---|
Rated Voltage | 325KV | Designed for 300KV systems with 8.3% safety margin |
Capacitance | 400pF | Enhanced signal coupling for PLC applications |
Voltage Ratio | 1000:1 | Industry-standard measurement scaling |
Accuracy | ≤±1% | Meets protection-class measurement requirements |
Partial Discharge | ≤5pC @325KV | Enables sensitive PD measurements |
Dielectric Loss | <0.3% | Minimizes signal attenuation |
Temp Coefficient | <0.0005 | Stable across -40°C to +55°C range |
Overvoltage | 357.5KV for 60s | 110% rated voltage withstand capability |
Operation Cycle | 15min ON/15min OFF (8 cycles/day max) | Optimized thermal management |
Dual-Function Performance
As Voltage Divider
Class 1 measurement accuracy (≤±1%)
Ultra-low ≤5pC partial discharge
1000:1 ratio compatible with all standard relays
As Coupling Capacitor
400pF optimized capacitance for carrier frequencies
Low loss design (<0.3%) maximizes signal transmission
SF6 insulation prevents corona interference
Thermal Management System
Intermittent Operation: 15-minute active periods prevent gas overheating
Cooling Cycles: 15-minute rest periods ensure dielectric recovery
Daily Limit: Maximum 8 cycles (4 hours total operation)
Thermal Monitoring: Built-in temperature sensors (optional)
Installation Guidelines
Mount on stable foundation (max 0.15g vibration tolerance)
Maintain SF6 pressure at 0.43±0.02MPa at 20°C
PLC connections require:
Bandpass filters (30-500kHz recommended)
Surge protection devices
Grounding resistance <3Ω (measured at 25Hz)
Maintenance Schedule
Frequency | Procedure | Acceptance Criteria |
---|---|---|
Weekly | Gas density check | 0.41-0.45MPa |
Monthly | Partial discharge test | ≤5pC @325KV |
Quarterly | Capacitance verification | 400pF ±2% |
Annually | Full dielectric test | Loss <0.3%, withstand 357.5KV |
Compliance Standards
IEC 60358-1:2012 (Coupling capacitors & dividers)
IEEE C93.3-2019 (Power line carrier coupling)
GB/T 4109-2008 (Chinese HV capacitor standard)
IEC 61869-11:2018 (Instrument transformers)
Critical Notice: Exceeding 8 daily operation cycles may cause SF6 gas decomposition and permanent dielectric strength reduction. Always allow complete cooling between cycles.