Gas Insulated Divider
300KV/2000pF SF6 Gas-Insulated Capacitor Voltage Divider & Coupling Capacitor
This innovative device combines high-accuracy voltage measurement with power line carrier (PLC) communication capabilities in a single SF6-insulated package, designed for smart grid applications.
Technical Specifications
Parameter | Specification | Functional Significance |
---|---|---|
Rated Voltage | 300KV | 330KV systems with 10% safety margin |
Capacitance | 2000pF | Optimal for PLC signal coupling (30-500kHz) |
Voltage Ratio | 1000:1 | Standard measurement scaling |
Accuracy | ≤±1% | Meets Class 1 metering requirements |
Dielectric Loss | <0.3% | Minimal signal attenuation |
Temp Coefficient | <0.0005 | Stable performance across climates |
Withstand Test | 330KV for 60s | 110% rated voltage safety factor |
Daily Operation | 20 minutes | Continuous PLC communication capability |
Dual-Function Design Advantages
As Voltage Divider
Precision ±1% measurement accuracy
1000:1 standard ratio for protection relays
SF6 insulation ensures measurement stability
As Coupling Capacitor
2000pF optimized for carrier frequencies
Low dielectric loss (<0.3%) minimizes signal loss
Integrated design reduces substation footprint
Typical Applications
Smart Grid Communication
Power line carrier (PLC) systems
SCADA data transmission
Substation Monitoring
Combined voltage measurement & communication
Digital relay systems
High Voltage Testing
Power factor testing
Dielectric loss measurements
Installation Guidelines
Mount vertically with ±3° tolerance for gas uniformity
Maintain SF6 pressure at 0.45±0.05MPa (at 20°C)
Use double-shielded cables for measurement circuits
PLC connections require impedance matching networks
Maintenance Schedule
Interval | Action | Parameters |
---|---|---|
Monthly | Gas pressure check | 0.40-0.50MPa |
6 Months | Dielectric loss test | <0.3% at rated voltage |
Annually | Capacitance verification | 2000pF ±5% |
Compliance Standards
IEC 60358 (Coupling capacitors & voltage dividers)
IEC 60481 (Coupling devices for PLC)
IEEE C93.1 (Coupling capacitors for power systems)
DL/T 629 (Chinese standard for power line carrier)
Note: When used for PLC, ensure carrier frequency is within 30-500kHz range and signal power <20W to prevent capacitor overheating.