Gas Insulated Divider
250KV/20pF SF6 Gas-Insulated Capacitor Voltage Divider Technical Specifications
This high-performance voltage divider combines SF6 gas insulation with ultra-low 20pF capacitance design, making it ideal for sensitive measurement applications in high-voltage testing and power system monitoring.
Key Technical Parameters
Parameter | Specification | Technical Significance |
---|---|---|
Rated Voltage | 250KV | Designed for 220KV-class systems with safety margin |
Rated Capacity | 20pF | Ultra-low loading effect on measured circuits |
Dividing Ratio | 2000:1 | High-ratio measurement for protection systems |
Frequency Range | 30-300Hz | Wide-frequency operation beyond power frequency |
Accuracy | ≤±1% | Class 1 precision for metering applications |
Dielectric Loss | <0.3% | Excellent insulation performance |
Partial Discharge | ≤5pC@250kV ≤3pC@200kV | Exceptional PD performance for sensitive environments |
Temp Coefficient | <0.0005 | Outstanding thermal stability |
Advanced Design Features
SF6 Gas Capacitor Technology
Conducting rod forms gas capacitor with SF6 insulation
Maintenance-free sealed gas system
Compact design compared to conventional dividers
Non-flammable insulation medium
Enhanced Performance Characteristics
Extended operation: 60 minutes continuous at 100% rated voltage/current
Rigorous insulation testing: Withstands 275kV for 60 seconds without abnormality
Wide-frequency measurement: 30-300Hz range covers harmonics analysis
Ultra-low PD: ≤5pC at rated voltage ensures measurement integrity
Typical Applications
High Voltage Laboratories
Reference standard for calibrations
Impulse voltage measurements
Power Grid Monitoring
EHV transmission line measurements
Harmonics analysis up to 300Hz
Transformer Testing
Applied voltage monitoring
Partial discharge measurements
Installation & Maintenance
Requires SF6 gas density monitoring system (typical pressure 0.4-0.6MPa)
Install with proper electrostatic shielding for accurate measurements
Annual dielectric loss measurement recommended
Periodic verification of voltage ratio accuracy
Compliance Standards
IEC 60060-1 (High-voltage test techniques)
IEC 61869-11 (Low-power passive voltage transformers)
IEEE Std 4-2013 (Standard for HV testing)
GB/T 16927.1 (Chinese national standard for HV testing)
Note: For optimal performance, the measuring instrument should have input impedance ≥100MΩ to maintain specified accuracy with this ultra-low capacitance divider.