Relay Tester/Secondary Circuit Tester
LQHV-1201 Six-Phase Relay Protection Test Set
Industrial-Grade Protection Relay Testing Solution
Designed to meet GB/T 7261-2016 and DL/T 624-2023 standards, the LQHV-1201 delivers unprecedented 6-phase voltage and 6-phase current output in a compact, portable package. Ideal for testing complex protection schemes including transformer differential and busbar protection systems.
Product Parameters
Current channel number | Standard 6 phase |
Voltage channel number | Standard 6 phase |
AC current output range | 30A/phase or 180A (six parallel) |
DC current output range | 10ADC/phase |
AC voltage output range | 120VAC/phase |
DC voltage output range | 160VDC/phase |
AC current output
6 phase current output per phase (effective value) | 0 ~ 30A output precision 0.2 |
3 phase current output per phase (effective value) | 0~60A |
6 phase parallel current output (RMS) | 0~180A |
Phase current long-term allowable working value (RMS) | 10A |
Maximum output power of phase current | 300VA |
6 phase parallel current maximum output power) | 1000VA |
6 Allowable working time for maximum output of phase parallel current | 10s |
Frequency range (fundamental) | 0~1000Hz |
Harmonic frequency | 1~20 |
DC current output
Current output | 0 ~ ±10A/phase output accuracy 0.5 level |
Maximum output load voltage | 20V |
AC voltage output
Phase voltage output (RMS) | 0 ~ 120V output precision 0.2 |
Line voltage output (RMS) | 0~240V |
Phase voltage/line voltage output work | 80VA/100VA |
Frequency range (fundamental) | 0~1000Hz |
Harmonic frequency | 1~20 |
DC voltage output
Phase voltage output amplitude | 0 ~ ±160V output accuracy 0.5 |
Line voltage output amplitude | 0~±320V |
Phase voltage/line voltage output power | 70VA/140VA |
Switching value
8 switch inputs | Null contact 1 ~ 20mA, 24V |
Potential contact access "0" : 0 ~ +6V; 1: +11 V to +250 V | |
4 pairs of switching output | DC:220 V/0.2 A;AC:220 V/0.5 A |
Time measuring range
Time measuring range | 0.1ms ~ 9999s |
Measurement accuracy | 0<0.1mS |
Volume | 375×350×180 (mm3) |
Unit weight | 17kg |
Key Specifications
Output Capacity: 6×120V (phase), 6×40A continuous (120A short-time)
Control System: DSP processor with 16-bit DAC resolution
Display: 10.1" TFT LCD (1280×800) with Windows interface
Accuracy: ±0.1% voltage, ±0.2% current, ±0.3° phase
Communication: Dual USB 3.0, RS232, Ethernet
Innovative Testing Capabilities
1. Six-Phase Flexible Output Matrix
12-phase combined output modes (6V+6C configuration)
Native support for 3-winding transformer differential tests
Programmable sequence output for auto-reclose simulations
2. DSP Digital Signal Processing
5μs real-time processing speed
0.01% THD at full load
0.1Hz–5kHz frequency bandwidth
3. Linear Amplifier Technology
High-fidelity output with <1μV noise floor
Active impedance matching (0.1Ω–10kΩ)
Forced-air cooling with thermal monitoring
Workflow Advantages
Dual Operation Modes
Standalone or PC-connected via USB/Ethernet
Automated Testing
30+ pre-loaded test templates
Data Management
Real-time storage and PDF report generation
Safety & Reliability
IP52-rated enclosure for field use
Multi-stage thermal protection (70°C auto-throttling)
Isolated DC outputs (220V/5A, 110V/10A)
Why Choose LQHV-1201?
Time Savings - 6-phase testing reduces project time by 65%
Future-Ready - Firmware upgradable via USB
Regulatory Compliance - Full GB/T 7261 test documentation