>400kV Range
LQHDR Series: 800kV/5kΩ Precision Damping Resistor
Engineered for critical high-voltage testing applications requiring ultra-low partial discharge levels and stable performance at extreme voltages.
Technical Specifications
Parameter | Specification |
---|---|
Rated Voltage | 800kV AC/DC |
Nominal Resistance | 5kΩ ±0.75% |
Rated Current | 0.5A |
Rated Power | 20kW at 50Hz |
Partial Discharge (PD) Level |
|
Operating Duration | 30 minutes at 100% rated voltage/current |
Temperature Rise | <100K at continuous 100% load |
Performance Highlights
Ultra-Low Partial Discharge
Industry-leading PD performance certified per IEC 60270:
<5pC at full 800kV test voltage
<3pC at 640kV (80% UH)
EMI-shielded measurement connections
High-Power Thermal Management
Maintains <100K temperature rise at 20kW power dissipation through:
Optimized forced-air cooling channels
Ceramic-encased resistance elements
Distributed heat-sink geometry
Structural Design Features
Multi-Stage Shielding: Triple corona rings at critical voltage points
Modular Construction: Stackable sections for transport and maintenance
Precision Winding: Nickel-chromium alloy on high-dielectric cores
EMI Containment: Integrated Faraday cage elements
Critical Applications
Ultra-high-voltage transformer PD testing
GIS (Gas-Insulated Substation) commissioning
HVDC converter station dielectric verification
Power cable system partial discharge measurement
High-energy research facility test systems
Performance Verification Data
Test Condition | Result |
---|---|
Continuous 800kV operation | 30 minutes stable (±0.5% resistance) |
Thermal imaging at 20kW | Max hotspot: 98K above ambient |
PD measurement at 640kV | 2.7pC average (IEC 60270 compliant) |
Impulse withstand | 1.2MV/50µs lightning impulse |
Safety & Compliance
IEC 60060-1:2010 High-voltage test techniques
IEEE 4-2013 Standard for HV testing
IEC 60270:2015 Partial discharge measurements
EN 62155:2003 Hollow pressurized ceramic insulators
Installation Requirements
Minimum 3.8m clearance to grounded objects
Dedicated 150A cooling system power supply
Ambient temperature ≤35°C during operation
Monthly infrared thermography inspections
Biannual calibration certification required
Voltage-PD Performance Relationship
Test Voltage | Max PD Level |
---|---|
100% (800kV) | <5pC |
90% (720kV) | <3.5pC |
80% (640kV) | <3pC |