>400kV Range
LQHDR 1000kV/5kΩ/0.67A ONAN-Cooled Damping Resistor
Electrical Specifications
Parameter | Specification | Standard |
---|---|---|
Rated Voltage | 1000kV AC | IEC 60273 |
Nominal Resistance | 5kΩ ±0.3% | IEEE 4-2013 |
Rated Current | 0.67A | IEC 60076 |
Power Rating | 2.2445kW | Thermal Class A |
Frequency | 50Hz | IEC 60060-1 |
Partial Discharge Performance
<5pC at 100% rated voltage (1000kV)
<3pC at 80% rated voltage (800kV)
Measured per IEC 60270 Class I precision
Ultra-low discharge characteristics ensure measurement integrity in sensitive high-voltage circuits.
Cyclic Operation Capability
Duty Cycle: 15 minutes ON / 15 minutes OFF
Maximum Cycles: 8 per 24-hour period
Optimized for intermittent high-stress test sequences in laboratory environments.
ONAN Cooling System
Cooling Method: Oil Natural Air Natural (ONAN)
Oil Capacity: 220L mineral oil (IEC 60296)
Thermal Capacity: 2.5kW heat dissipation
Cooling Surface: 8m² corrugated radiator
The passive cooling system ensures zero-maintenance operation with natural convection.
Thermal Performance
Stabilizes within 15 minutes of operation
15-minute cooldown period between cycles
Oil temperature rise maintained below 55K
Cyclic Duty Applications
Intermittent transformer impulse testing
Batch testing in high-voltage laboratories
Research facility validation cycles
Quality assurance sampling systems
Prototype evaluation test sequences
Operational Protocol
Pre-cycle insulation test (min 50GΩ at 5kV DC)
Maximum 8 cycles per 24-hour period
15-minute minimum cooldown between operations
Annual oil dielectric strength verification
Safety & Reliability Features
Pressure-relief membrane for oil expansion
Corona-free design up to 1100kV
Dual moisture sensors in oil compartment
Grounding terminals with 10mm² minimum requirement
Compliance Standards
IEC 60273: High-voltage resistors
IEEE 4-2013: HV testing standards
EN 60076-14: Liquid-immersed equipment
IEC 61010-1: Safety requirements