>400kV Range
LQHDR 1200kV/20kΩ/0.5A Damping Resistor: Thermal Innovation
Electrical Specifications
Parameter | Value | Standard |
---|---|---|
Rated Voltage | 1200kV AC | IEC 60273 |
Nominal Resistance | 20kΩ ±0.5% | IEEE 4-2013 |
Rated Current | 0.5A continuous | IEC 60076 |
Power Rating | 1.5kW | Thermal Class F |
Frequency | 50Hz | IEC 60060-1 |
Graded Partial Discharge Performance
Voltage Level | Partial Discharge | Percentage |
---|---|---|
1200kV | <10pC | 100% rated voltage |
960kV | <5pC | 80% rated voltage |
720kV | <3pC | 60% rated voltage |
Tested per IEC 60270 with shielded measurement environment.
Honeycomb Thermal Management System
Core Construction: Nickel-chromium wire precision-wound on epoxy composite boards
Hexagonal Structure: Open-cell honeycomb configuration maximizes surface area
Heat Exchange Efficiency: 45% greater cooling than solid-core designs
Material Integrity: Maintains mechanical strength at operational temperatures
The honeycomb design ensures uniform air convection, limiting temperature rise to <100K during 60-minute continuous operation at full load.
Triple-Shielding Protection System
End-Ring Electrodes: Dual 350mm-radius aluminum rings at terminals
Central Grading Ring: Positioned at midpoint with optimized curvature
Discharge Protection: Controls electric field distribution during test object breakdown
Prevents insulation damage by directing discharge energy away from critical components.
Operational Performance
Continuous Operation: 60 minutes at 1200kV/0.5A (1.5kW)
Thermal Recovery: 90-minute cooldown between full-power tests
Resistance Stability: ±0.15% maximum deviation during thermal transients
Structural Advantages
Feature | Technical Benefit |
---|---|
Nickel-Chromium Alloy | Temperature coefficient <10ppm/°C up to 300°C |
Epoxy Composite Boards | Comparative Tracking Index (CTI) >600V per IEC 60112 |
Honeycomb Configuration | Surface area-to-volume ratio: 18m²/m³ |
High-Voltage Applications
UHV transformer impulse testing (IEC 60076)
Gas-insulated switchgear (GIS) diagnostics
Lightning surge generator systems
High-energy physics research facilities
HVDC converter station validation
Safety & Maintenance Protocols
Pre-operation inspection of honeycomb integrity
Annual shielding ring alignment verification
Resistance calibration every 500 operating hours
Infrared thermography during commissioning
Dielectric strength test every 2 years
Compliance Standards
IEC 60273: High-voltage resistors
IEEE 4-2013: HV testing techniques
EN 62217: Polymeric HV insulators
IEC 60112: Tracking resistance standards
IEC 60071: Insulation coordination