High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

>400kV Range

LQHDR 800kV/5kΩ/2A Damping Resistor | 20kW High-Current HV Test Component | <2pC PD Level

Technical specifications for LQHDR 800kV/5kΩ damping resistor: 2A current rating, 20kW power capacity, and <2pC PD level for ultra-high-voltage testing.


  • Negotiated Price
  • Lead time: 30days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHDR Series: 800kV/5kΩ High-Power Damping Resistor

Engineered for extreme high-voltage/high-current applications, this 20kW damping resistor sets new standards for PD performance and thermal management in critical test systems.

Technical Specifications

ParameterSpecification
Rated Voltage800kV AC/DC
Nominal Resistance5kΩ ±0.8%
Rated Current2A continuous
Rated Power20kW at 50Hz
Partial Discharge (PD) Level<2pC at rated voltage
Operating Duration60 minutes at 100% rated voltage/current
Temperature Rise<120K at continuous 100% load

Performance Highlights

Industry-Leading PD Performance

Ultra-low <2pC partial discharge level at 800kV ensures precision measurements during dielectric tests, exceeding IEC 60270 Class I requirements.

High-Current Capability

2A continuous current rating enables testing of high-energy systems previously requiring multiple parallel resistors.

Advanced Thermal Design

Optimized heat dissipation maintains surface temperature rise below 120K at full 20kW load, featuring:

  • Forced-air cooling channels

  • High-thermal-conductivity materials

  • Temperature-monitored hot spots

Structural Features

  • Robust Construction: Nickel-chromium alloy resistance elements on ceramic-insulated cores

  • Multi-Point Shielding: Triple corona rings minimize discharge interference

  • Modular Design: Stackable sections for transportation and maintenance

  • EMI Suppression: Integrated Faraday cage elements

Industrial Applications

  • Ultra-high-voltage transformer impulse testing

  • HVDC converter station commissioning

  • Nuclear fusion research equipment

  • High-power laboratory test systems (>15MW)

  • Transmission line surge arrestor validation

Safety & Compliance

  • IEC 60060-1:2010 High-voltage test techniques

  • IEEE 4-2013 Standard for HV testing

  • EN 50191:2010 Erection and operation of electrical test equipment

  • Certified for 900kV power frequency withstand (1 minute)

Installation Requirements

  1. Minimum 3.5m clearance to grounded structures

  2. Dedicated 200A cooling system power supply

  3. Ambient temperature ≤35°C during operation

  4. Monthly IR thermography scans recommended

  5. Calibration every 6 months or 50 operations

Power Derating Guidelines

Ambient TemperatureMaximum Continuous Power
≤25°C100% (20kW)
30°C18kW
35°C15kW

>>>WhatsApp Communication<<<