>400kV Range
LQHDR 800kV/2.5kΩ Damping Resistor: Engineering Analysis
Core Technical Specifications
Parameter | Value | Standard |
---|---|---|
Rated Voltage | 800kV | IEC 60273 |
Nominal Resistance | 2.5kΩ | ±1% tolerance |
Rated Current | 1A | Continuous duty |
Rated Power | 2.5kW | Thermal Class H |
Rated Frequency | 50Hz | IEEE 4-2013 |
Partial Discharge Performance
≤3pC at 100% rated voltage (800kV)
≤2pC at 80% rated voltage (640kV)
Measured per IEC 60270 with shielded test environment
Ultra-low discharge levels ensure minimal electromagnetic interference during precision measurements.
Operational Duty Cycle
Cyclic Operation: 15 minutes ON / 15 minutes OFF
Maximum Cycles: 48 per 24-hour period
Designed for high-stress test environments like impulse voltage generators and HVDC systems.
Design & Construction Features
Dielectric Material: Silicone-impregnated fiberglass encapsulation
Cooling System: Natural convection with radial fins
Terminals: Electroplated copper connectors with anti-corrosion coating
Safety Rating: IP67 enclosure for dust/water resistance
Industrial Applications
Lightning impulse voltage generators (IEC 60060-1)
HVDC transmission system testing
Transformer impulse withstand validation
High-power laboratory test benches
Switchgear transient suppression
Safety & Maintenance Protocols
Pre-operational insulation resistance test (min 100GΩ at 5kV DC)
Infrared thermography during first 3 cycles
Annual recalibration per ISO/IEC 17025
Dielectric strength verification at 960kV (120% rated voltage)
Compliance Standards
IEC 60273: High-voltage resistors
IEEE 4-2013: HV testing standards
EN 60076: Power transformer testing
OSHA 1910.269: Electrical safety requirements