LQHVF 60kV/1000pF Coupling Capacitor & Capacitive Voltage Divider
High-capacitance solution for precision power system monitoring featuring industry-leading dielectric loss performance and flexible dual-stage measurement capability. Engineered for substation monitoring, harmonic analysis, and HV research applications.
Core Technical Specifications
Rated Voltage: 60kV AC RMS
Nominal Capacitance: 1000pF
Dividing Ratio: 1000:1 (±1% accuracy)
Frequency: 50/60Hz (40-1000Hz range)
Dielectric Loss: <0.2% @ 25°C (industry best)
Partial Discharge: <5pC at 60kV
Cooling System: ONAN (Oil Natural Air Natural)
Insulation Withstand: 66kV/1min (110% rated voltage)
Operating Duration:
60 minutes continuous @ 100% rated voltage
Continuous operation @ 80% rated voltage
Innovative Structural Design
Optimized Components
Aluminum Corona Rings: Lightweight alloy construction reduces shipping weight by 40% while preventing corona discharge
Removable Pedestal: Engineered for stability with quick-release mechanism for field maintenance
HV Connection System: Corona-free scalable terminals support single-stage and dual-stage configurations
Measurement Versatility
Specialized lead-wire system connects directly to variable frequency power sources:
Single-Stage Mode: Standard 1000:1 division for routine monitoring
Dual-Stage Series Mode: Extended voltage range for specialized testing
Frequency Response: Maintains accuracy from 40Hz to 1kHz
Performance Validation
Test Parameter | Standard | Performance |
---|---|---|
Dielectric Loss | IEC 60250 | <0.18% @ 50Hz/25°C |
Partial Discharge | IEC 60270 | <4.2pC @ 60kV |
Temperature Rise | IEEE C57.19.00 | 32°C above ambient @ full load |
Impulse Withstand | IEC 60060-1 | 170kV (1.2/50μs wave) |
Compliance: Meets IEC 61869-11, IEEE C57.13, and ANSI C93.1 standards.
Advanced Applications
Power Quality Analysis
Harmonic distortion measurement
Transient overvoltage capture
Voltage flicker analysis
Protective Relay Testing
Distance relay calibration
Differential protection verification
Synchrophasor measurement
Research & Development
Dielectric material studies
HF transient analysis
Power electronics interface testing
Operational Advantages
Ultra-Low Loss: <0.2% dielectric loss enables precise energy measurements
Measurement Flexibility: Dual-stage configuration supports diverse testing scenarios
Transport Optimized: Aluminum components reduce shipping costs by 30%
Maintenance Ready: Removable base allows onsite oil servicing
Frequency Agile: Maintains accuracy up to 1kHz for power electronics applications
Connection & Installation
Wiring Configuration
LV Measurement: Shielded coaxial cable with BNC connectors
HV Input: Corona-free terminals accept 25-50mm connectors
Power Source Interface: Dedicated leads for variable frequency supplies
Grounding Protocol
Establish dual-point ground connection to base plate
Verify continuity (≤0.1Ω resistance)
Connect safety ground before energizing