400kV ~ 600kV Range
LQHVF 600kV/1500pF Dual-Function System: Coupling Capacitor & Capacitive Voltage Divider
Precision High-Voltage Measurement & Energy Transfer
Engineered for critical power infrastructure applications, the LQHVF 600kV/1500pF system combines coupling capacitor functionality with precision voltage measurement in a single integrated solution. With its 2000:1 dividing ratio and industry-leading ≤1% accuracy, this dual-purpose system delivers unmatched performance in high-voltage testing environments.
Technical Specifications
Parameter | Specification | Standard Compliance |
---|---|---|
Rated Voltage | 600kV AC @ 50Hz | IEC 60060-1 |
Nominal Capacitance | 1500pF ±10% | IEC 60137 |
Dividing Ratio | 2000:1 | IEEE 4 |
Dielectric Loss | <0.2% @ 20°C | IEC 60247 |
Partial Discharge | <5pC @ 600kV (100% UH) | IEC 60270 |
Insulation Withstand | 660kV (110%) for 1 minute | IEC 60071-2 |
Measuring Accuracy | ≤1% | IEC 61869-11 |
Continuous Operation | 60 minutes @ 600kV | ANSI C57.12.90 |
Dual-Functional Operation
Coupling Capacitor Mode
Efficient energy transfer for power line carrier (PLC) communication systems with 1500pF coupling capacitance and <0.2% dielectric loss.
Voltage Divider Mode
Precision measurement with 2000:1 ratio and ≤1% accuracy for high-voltage testing applications.
Advanced Engineering Features
Aluminum Corona Rings
Lightweight alloy corona suppression rings ensure corona-free operation up to 660kV while enabling compact transportation.
Removable Stabilizing Pedestal
Engineered base provides exceptional field stability with quick-disconnect functionality for rapid deployment.
Multi-Configuration Measurement
Special lead-wire system enables:
Single-stage and two-stage serial voltage measurement
Compatibility with variable frequency power sources
Scalable corona-free HV connections
ONAN Cooling Technology
Oil-Natural Air-Natural thermal management maintains stable operation during extended 600kV testing.
Industry Applications
Power Transmission
Line coupling for PLC communication in 500kV+ transmission networks
Substation Testing
Precision voltage measurement during circuit breaker timing tests
Cable Testing
Resonant test systems for XLPE cable commissioning at 50Hz
Research Laboratories
Reference standard for high-voltage meter calibration
Performance Validation
Partial Discharge Test: Certified <5pC at 600kV per IEC 60270
Dielectric Strength: 1-minute withstand at 660kV with zero discharge events
Thermal Stability: ≤15°C oil temperature rise during 60-minute continuous operation
Ratio Accuracy: Verified with NIST-traceable calibration sources
Safety & Compliance
Clearance distances: IEEE 1308-2020
Dielectric testing: IEC 60060-1/-2
Partial discharge: IEC 60270 Class II
Environmental protection: IP65 (outdoor operation)
Safety certifications: UL 61010-1, CE, RoHS