<100kV Range
LQHVF 50kV/500pF Capacitive Voltage Divider & Coupling Capacitor
Industry-Leading Efficiency: Ultra-low <0.2% dielectric loss for precision measurements in 50kV systems at 60Hz
Precision Instrument for Extra-High Voltage Systems
Engineered for critical 50kV/60Hz applications, the LQHVF delivers laboratory-grade accuracy with field-deployable reliability. The optimized 500pF capacitance provides:
Ultra-low dielectric dissipation (<0.2%)
Precise voltage measurement with ≤±1% accuracy
Partial discharge detection within complete test systems
Superior thermal stability with ONAN cooling
50kV
Technical Specifications
Parameter | Specification | Performance Advantage |
---|---|---|
Rated Voltage | 50kV | EHV system compatibility |
Frequency | 60Hz | North American power system standard |
Capacitance | 500pF | Optimal balance for PD coupling & measurement |
Voltage Ratio | 1000:1 | 50V output at 50kV input |
Dielectric Loss | <0.2% | Industry-leading insulation efficiency |
Partial Discharge | <10pC @ 100% UH | IEC 60270 compliant system performance |
Accuracy | ≤±1% | Meets IEEE 4-2013 Class 0.5 standards |
Operating Time | 60min @ 50kV | Full-power diagnostic capability |
Advanced PD Test System Performance
Complete Test System Integration
The <10pC PD specification applies to the entire measurement chain, including:
Coupling capacitor (this unit)
Measurement impedance
PD analyzer
Shielding and grounding system
Calibration Requirement: System verification per IEC 60270 using calibrated pulse injector
Innovative Structural Design
Corona Rings
Optimized geometry
Removable design
Ly Arm
Measurement interface
BNC output
Hy Arm
High-voltage terminal
50kV rated
Removable Base
Stabilized platform
Leveling feet
Oil-Immersed Construction
High-grade mineral oil with dielectric strength >60kV/mm
Benefit: Enhanced arc suppression and thermal management
Modular Design
Quick-disconnect components
Benefit: 10-minute field assembly
ONAN Cooling
Natural oil/air convection
Benefit: Stable operation at full load
Dual-Function Operation
Voltage Division
Application: RMS voltage measurement
Accuracy: ≤±1% at 60Hz
Output: 50V at 50kV input
PD Coupling
Application: Partial discharge detection
Sensitivity: <10pC system performance
Bandwidth: 30Hz-500kHz
Technical Note: The 500pF capacitance provides optimal impedance for 50kV/60Hz systems, balancing PD sensitivity and high-frequency response
Thermal Management
ONAN System: Oil Natural Air Natural cooling
Thermal Performance: <50°C rise during 60-min operation
Operating Protocol:
60 minutes continuous at 50kV (100% UH)
Followed by 90-minute cooling period
Cooling Requirements: 30cm clearance around unit
Compliance & Applications
Standards Compliance: IEC 60270:2000 (PD), IEEE 4-2013 (Testing), ANSI C57.13 (Accuracy)
Critical Applications:
Factory acceptance testing of 50kV switchgear
On-line PD monitoring in substations
Dielectric loss measurement in power transformers
High-voltage research at 60Hz
Calibration of protective relays
Operational Protocol
Preparation
Assemble components on stable surface
Connect Ly-arm to measurement device
Ground base with ≥12mm² cable
Energization
Ramp voltage gradually (≤5kV/s)
Monitor for 60 minutes maximum
Verify oil temperature <85°C
PD Measurement
Connect to PD analyzer via Ly-arm
Calibrate system with pulse injector
Use double-shielded coaxial cables
Shutdown
De-energize system
Wait 10 minutes for discharge
Disassemble components
Why This Instrument?
Dielectric Precision
<0.2% loss for accurate measurements
System Integration
<10pC PD system performance
Thermal Stability
ONAN cooling for continuous operation
Frequency Optimized
Designed for 60Hz power systems