<150kV Range
LQHDR Series: 50kV/10KΩ/0.14A Precision Damping Resistor
Critical Component for High-Voltage Systems
The LQHDR damping resistor provides essential surge protection in transformer testing, switchgear diagnostics, and partial discharge measurement systems. Engineered for 50kV applications with ultra-low PD levels, it ensures signal integrity in demanding electrical environments.
Technical Specifications
Parameter | Specification | Standard |
---|---|---|
Model | LQHDR | IEC 60270 Compliant |
Rated Voltage | 50kV AC | |
Nominal Resistance | 10KΩ ±1% | |
Rated Current | 0.14A | |
Partial Discharge (PD) | <5pC @ 50kV | |
Frequency Rating | 50Hz | |
Power Rating | 700W (calculated from V×I) |
Operational Parameters
Thermal Performance
Full load operation: 60 minutes continuous @ 100% rated voltage
Sustained operation: Continuous @ 80% rated voltage/current
Max. temperature rise: ≤80K (resistor body) @ 100% load
System Temperature Limits
Transformer windings: ≤65K temperature rise
Oil surface: ≤55K temperature rise
Key Applications
⚡ Transformer Testing Systems
Provides precise damping for dielectric tests and PD measurements on power transformers up to 132kV class.
🔬 Partial Discharge Detection
Ensures measurement accuracy with <5pC background noise during critical HV cable and GIS testing.
🏭 Impulse Voltage Circuits
Controls wavefront timing in lightning impulse generators (1.2/50μs) per IEC 60060-1 standards.
Design Features
Low-inductance design: Minimizes waveform distortion at 50Hz
Oil-immersed construction: Mineral oil cooling for thermal stability
Corona-free terminals: Silicone-insulated connectors (70kV BIL)
Modular stacking: Series connection for voltages up to 400kV
Safety & Maintenance
Perform dielectric tests annually: >1000MΩ @ 5kV DC
Verify resistance tolerance (±1%) every 6 months
Monitor oil quality per IEC 60296 standards
Calibrate with reference divider per IEC 60060-2
Important: Always maintain proper grounding - NFPA 70E requires ground verification before HV testing.