<150kV Range
LQHDR Series 100kV/10kΩ/0.25A Extended-Run Damping Resistor
Engineered for long-duration high-voltage testing applications requiring stable performance and ultra-low partial discharge in a lightweight package.
Technical Specifications
Parameter | Specification |
---|---|
Rated Voltage | 100kV AC (50/60Hz) |
Nominal Resistance | 10kΩ ±1% |
Rated Current | 0.25A continuous |
Power Rating | 25kW (intermittent) |
Partial Discharge | <5pC at 100kV |
Max Temperature Rise | ≤80K at 100% load |
Full-Load Operation | 60 minutes at 100kV/0.25A |
Continuous Operation | Unlimited at 80kV/0.2A (80% rating) |
Dimensions | Ø70/115mm × 850mm (tapered design) |
Weight | <5kg |
Dielectric Strength | 120kV/1min (IEC 60243) |
Key Performance Features
Extended Operation: 60-min full-power capability + unlimited operation at 80% rating
Ultra-Lightweight: Advanced composite materials enable <5kg weight (40% lighter than conventional models)
Stable PD Performance: <5pC partial discharge maintained throughout operating cycle
Efficient Cooling: Aerodynamic fin design ensures ≤80K temperature rise without forced air
Low Inductance: <3μH for accurate high-frequency response
Operational Modes
Full-Power Mode
Voltage: 100kV
Current: 0.25A
Duration: 60 minutes max
Cooling: 120 min cooldown required
Continuous Mode
Voltage: 80kV (80%)
Current: 0.2A (80%)
Duration: Unlimited
Temp Rise: ≤50K
Mechanical Design
Tapered Profile: Ø70mm (terminals) to Ø115mm (center) for optimized electric field distribution
Lightweight Construction: Carbon-fiber reinforced polymer core
Terminals: Dual corona-free silicone connectors
Mounting: Integrated M10 mounting points at both ends
Environmental Rating: IP55 (dust/water resistant)
Application Scenarios
Extended-Duration Testing
Transformer temperature rise tests
Long-term cable aging studies
Dielectric absorption measurements
Field Testing
Mobile HV test laboratories
Substation commissioning
Renewable energy farm maintenance
Installation Guidelines
Mount vertically or horizontally with minimum 40cm clearance
Use HV silicone cables (min. 16mm² cross-section)
Ensure ambient temperature ≤40°C for full-power operation
Ground terminal resistance <0.5Ω
For ceiling mounting: Use safety cable (max. 1m length)
Compliant with IEC 61010-1:2010 safety standards for HV equipment.
Thermal Performance
Operation Level | Duration | Temperature Rise |
---|---|---|
100% (100kV/0.25A) | 60 min | ≤80K |
90% (90kV/0.225A) | 120 min | ≤70K |
80% (80kV/0.2A) | Continuous | ≤50K |
Natural convection cooling sufficient for all operating modes.
Maintenance Protocol
Pre-Use: Visual inspection and IR test (2.5kV DC, min. 100GΩ)
Monthly: Terminal cleaning with non-conductive solvent
Bi-Annual: Full calibration per IEC 60060-2
After Full-Power Use: 2-hour cooldown before storage