High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

<150kV Range

LQHDR 100kV/0.5A Damping Resistor - 10kΩ High Power HV Resistor with <2pC PD Level

High-power 100kV/10kΩ damping resistor rated for 0.5A with <2pC partial discharge. Features 15-min continuous operation, ≤80K temperature rise, and compact design (850mm). Ideal for demanding HV applications.


  • US$ 1,395.00
  • Lead time: 30days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHDR Series 100kV/10kΩ/0.5A High-Current Damping Resistor

Engineered for high-power applications requiring exceptional thermal management and minimal partial discharge in demanding test environments.

Technical Specifications

ParameterSpecification
Rated Voltage100kV AC (50/60Hz)
Nominal Resistance10kΩ ±0.5%
Rated Current0.5A continuous
Power Rating50kW peak
Partial Discharge<2pC at 100kV
Max Temperature Rise≤80K at full load
Duty Cycle15 minutes ON / 45 minutes OFF at 100% load
DimensionsØ70/115mm × 850mm (tapered design)
Weight<15kg
Dielectric Strength150kV/1min (IEC 60243)

Key Performance Features

  • Ultra-Low PD Design: Specialized grading rings ensure <2pC partial discharge at rated voltage

  • High Power Density: 50kW capability in compact 850mm form factor

  • Advanced Cooling: Aluminum core with forced-air convection slots maintains ≤80K rise

  • Impulse Resistant Withstands 250kV lightning impulse (1.2/50μs wave)

  • Low Inductance: <5μH design for accurate pulse waveform shaping

Mechanical Design

Optimized Geometry

  • Tapered Profile: Ø70mm (terminals) to Ø115mm (center) reduces corona effects

  • Mounting System: Dual M12 stainless steel flanges

  • Terminals: Corona-free silicone-coated HV connectors

Environmental Protection

  • IP54 rating for dust/moisture resistance

  • UV-resistant silicone housing

  • Operating temp: -30°C to +50°C

High-Current Applications

Power System Testing

  • Circuit breaker impulse testing

  • Transformer inrush current simulation

  • Generator coil withstand verification

Research & Development

  • Plasma ignition systems

  • Pulsed power experiments

  • High-energy capacitor banks

Thermal Performance Data

Operation ModeDurationTemperature Rise
Continuous @ 100%15 minutes≤80K
Cyclic (1:3 duty)8 hours≤95K peak
Short Pulse (10s)Unlimited cycles≤25K

Forced-air cooling recommended for cyclic operation exceeding 30 minutes/hour.

Installation & Safety

  1. Mount horizontally with minimum 60cm clearance to all surfaces

  2. Use only HV-rated cables (min. 25mm² cross-section)

  3. Implement external airflow (≥2m/s) for cyclic operation

  4. Ground both terminals via 10mm² copper straps

Compliant with IEC 61010-1:2010 safety requirements for high-power test equipment.

Maintenance Protocol

  • Daily: Visual inspection for surface contamination

  • Monthly: IR test (5kV DC) - minimum 50GΩ

  • Quarterly: Torque check on terminal connections (45Nm)

  • Annual: Full performance validation per IEC 60060-3

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<