<150kV Range
LQHDR Series 100kV/10kΩ/0.5A High-Current Damping Resistor
Engineered for high-power applications requiring exceptional thermal management and minimal partial discharge in demanding test environments.
Technical Specifications
Parameter | Specification |
---|---|
Rated Voltage | 100kV AC (50/60Hz) |
Nominal Resistance | 10kΩ ±0.5% |
Rated Current | 0.5A continuous |
Power Rating | 50kW peak |
Partial Discharge | <2pC at 100kV |
Max Temperature Rise | ≤80K at full load |
Duty Cycle | 15 minutes ON / 45 minutes OFF at 100% load |
Dimensions | Ø70/115mm × 850mm (tapered design) |
Weight | <15kg |
Dielectric Strength | 150kV/1min (IEC 60243) |
Key Performance Features
Ultra-Low PD Design: Specialized grading rings ensure <2pC partial discharge at rated voltage
High Power Density: 50kW capability in compact 850mm form factor
Advanced Cooling: Aluminum core with forced-air convection slots maintains ≤80K rise
Impulse Resistant Withstands 250kV lightning impulse (1.2/50μs wave)
Low Inductance: <5μH design for accurate pulse waveform shaping
Mechanical Design
Optimized Geometry
Tapered Profile: Ø70mm (terminals) to Ø115mm (center) reduces corona effects
Mounting System: Dual M12 stainless steel flanges
Terminals: Corona-free silicone-coated HV connectors
Environmental Protection
IP54 rating for dust/moisture resistance
UV-resistant silicone housing
Operating temp: -30°C to +50°C
High-Current Applications
Power System Testing
Circuit breaker impulse testing
Transformer inrush current simulation
Generator coil withstand verification
Research & Development
Plasma ignition systems
Pulsed power experiments
High-energy capacitor banks
Thermal Performance Data
Operation Mode | Duration | Temperature Rise |
---|---|---|
Continuous @ 100% | 15 minutes | ≤80K |
Cyclic (1:3 duty) | 8 hours | ≤95K peak |
Short Pulse (10s) | Unlimited cycles | ≤25K |
Forced-air cooling recommended for cyclic operation exceeding 30 minutes/hour.
Installation & Safety
Mount horizontally with minimum 60cm clearance to all surfaces
Use only HV-rated cables (min. 25mm² cross-section)
Implement external airflow (≥2m/s) for cyclic operation
Ground both terminals via 10mm² copper straps
Compliant with IEC 61010-1:2010 safety requirements for high-power test equipment.
Maintenance Protocol
Daily: Visual inspection for surface contamination
Monthly: IR test (5kV DC) - minimum 50GΩ
Quarterly: Torque check on terminal connections (45Nm)
Annual: Full performance validation per IEC 60060-3