LQHVF 50kV/100pF Capacitive Voltage Divider & Coupling Capacitor
Ultra-High Voltage Solution: Precision measurement and PD detection at 50kV with industry-leading ≤±1% accuracy
Designed for Critical Ultra-HV Applications
Engineered for power transmission and industrial systems, the LQHVF 50kV divider delivers laboratory-grade performance in field conditions. The optimized 100pF capacitance enables:
Accurate voltage measurement at extreme potentials
Sensitive partial discharge detection (<5pC)
Minimal circuit loading during measurements
High-frequency response up to 200kHz
50kV
Technical Specifications
Parameter | Specification | Performance Advantage |
---|---|---|
Rated Voltage | 50kV | Ultra-high voltage capability |
Capacitance | 100pF | Minimal circuit interference |
Voltage Ratio | 1000:1 | 50V output at 50kV input |
Partial Discharge | <5pC @ 50kV | Meets IEC 60270 Class I requirements |
Dielectric Loss | <0.5% | Superior insulation efficiency |
Accuracy | ≤±1% | Exceeds IEEE 4-2013 standards |
Operating Time | 60min @ 50kV | Full-power diagnostic capability |
Cooling System | ONAN | Natural oil/air convection |
Advanced Structural Design
Oil-Immersed Construction
High-grade mineral oil with dielectric strength >60kV/mm
Arc suppression and thermal stability
Removable Corona Rings
Precision-engineered aluminum alloy
Prevents surface discharge at extreme voltages
Modular Components
Quick-disconnect HV arm, V arm, and base
Field assembly in 10 minutes
Stabilized Base
Non-slip design with leveling feet
Secure operation on uneven surfaces
Ultra-HV Performance Features
Field Advantage: 100pF capacitance provides superior high-frequency response - essential for capturing lightning impulses and switching transients
Voltage Division
Accuracy: ≤±1% from DC to 50kHz
Phase Error: <0.1° at 50Hz
PD Detection
Sensitivity: <5pC at 50kV
Bandwidth: 20Hz-200kHz
Thermal Management System
ONAN Cooling: Oil Natural Air Natural convection maintains safe operating temperatures
Thermal Performance: <45°C rise during 60-min full-load operation
Operating Protocol:
60 minutes continuous at 50kV
Recommended 90-minute cooling period
Clearance Requirements: Maintain 30cm air space around unit
Compliance & Applications
Standards Compliance: IEC 60270:2000, IEEE 4-2013, EN 60060-1:2010
Critical Applications:
Testing of 50kV switchgear and GIS
Partial discharge monitoring in HV transformers
High-voltage research laboratories
Power quality analysis in transmission systems
Dielectric testing of insulation materials
Operational Protocol
Safety First
Grounding: 16mm² earth cable minimum
Clearance: Maintain 1m minimum personnel distance
Assembly
1. Secure base
2. Connect V-arm
3. Install HV arm
4. Attach corona rings
Operation
Ramp Rate: ≤5kV/s
Max Duration: 60min @50kV
Shutdown
1. De-energize
2. Wait 10min discharge
3. Disassemble
Pro Tip: For PD measurements at 50kV, use double-shielded coaxial cables and ferrite cores to suppress RF interference
Why Choose This Instrument?
Extreme Voltage Capability
Precision measurement at 50kV with ≤±1% accuracy
Superior Transient Response
100pF capacitance enables accurate capture of nanosecond events
Safety Assurance
Automatic discharge system with visual indicators
Thermal Resilience
ONAN cooling maintains stability during extended operation