400kV ~ 600kV Range
LQHVF 500kV/800pF Wide-Frequency Capacitive Voltage Divider
Precision measurement solution offering exceptional 30-300Hz frequency range with industry-leading ≤1% voltage ratio error for critical high-voltage applications.
Ultra-Precise Ratio: ≤1% voltage ratio error ensures measurement integrity in critical testing scenarios
Technical Specifications
Parameter | Specification | Test Standard |
---|---|---|
Rated Voltage | 500kV | IEC 60060-1 |
Frequency Range | 30Hz - 300Hz | IEC 60076-18 |
Rated Capacity | 800pF | IEEE 4 |
Voltage Ratio Error | ≤1% (effective value) | IEC 61869-5 |
Dielectric Loss | <0.5% | IEC 60422 |
Measuring Accuracy | ≤1.5% | IEEE 112 |
Dividing Ratio | 1000:1 | N/A |
Continuous Operation | 60 minutes @ 100% rating | IEEE C57.91 |
Insulation Withstand | 550kV (110% rated) for 60s | IEC 60071 |
Cooling System | ONAN (Oil Natural Air Natural) | IEEE C57.12.00 |
Precision Performance Features
Ultra-Accurate Voltage Ratio
≤1% voltage ratio error (effective value)
1000:1 nominal dividing ratio
Consistent across frequency range
Wide Frequency Operation
30-300Hz range for diverse applications
Stable performance across spectrum
Ideal for resonant testing and SFRA
Robust Insulation System
550kV withstand capability
ONAN cooling maintains stability
<0.5% dielectric loss
Advanced Engineering Design
Transport-Optimized Corona System
Aerospace-grade aluminum corona rings
Segmented design for packing
Corona-free HV connections
Removable Stability Pedestal
Engineered for seismic stability
Quick assembly/disassembly
Integrated measurement ports
Flexible Measurement System
Special lead-wire to VF power sources
Single/two-stage serial measurement
Scalable corona-free connections
Frequency Performance Validation
Frequency | Voltage Ratio Error | Measuring Accuracy |
---|---|---|
30Hz | ≤0.95% | ≤1.45% |
50/60Hz | ≤0.85% | ≤1.25% |
150Hz | ≤0.92% | ≤1.35% |
300Hz | ≤0.98% | ≤1.48% |
Tested at 500kV per IEEE 4 standards
Configuration Capabilities
Single-Stage Measurement
Direct high-accuracy measurement
Simplified setup
Full frequency range support
Two-Stage Serial Connection
Extended voltage range
Scalable configuration
Maintains precision specifications
Variable Frequency Compatibility
30-300Hz operation
Special lead-wire to VF sources
Optimized for resonant testing
Industry Applications
Transformer Frequency Response
Sweep Frequency Response Analysis (SFRA) up to 300Hz
Resonant Test Systems
Precision measurement in variable frequency resonant circuits
High-Power Research
Dielectric studies at multiple frequencies
Quality Assurance
Critical component validation with ≤1% ratio accuracy
Compliance & Certifications
IEC 60060-1: High-voltage test techniques
IEEE 4: Standard for HV testing
IEC 61869-5: Capacitor voltage transformers
IEC 60076-18: Frequency response testing
CE, RoHS, and UKCA certified
Safety Compliance: Meets IEEE 516-2022 safety requirements for 500kV installations