400kV ~ 600kV Range
LQHVF 500kV/500pF Dual-Function Capacitor Voltage Divider & Coupling Capacitor
Precision-engineered solution combining voltage measurement and partial discharge detection capabilities with industry-leading stability and ultra-low PD performance.
Ultra-Low PD Detection: ≤2pC partial discharge sensitivity at 400kV - ideal for critical insulation diagnostics
Technical Specifications
Parameter | Specification | Test Standard |
---|---|---|
Rated Voltage | 500kV | IEC 60060-1 |
Operation Frequency | 50Hz | IEC 60076 |
Capacitance | 500pF | IEEE 4 |
Partial Discharge @ 500kV | ≤5pC | IEC 60270 |
Partial Discharge @ 400kV | ≤2pC | |
Dielectric Loss | <0.5% | IEC 60422 |
Temperature Coefficient | <0.0005%/°C (5 ppm/°C) | IEC 60068 |
Measuring Accuracy | ≤±1.5% | IEEE 112 |
Dividing Ratio | 2000:1 | N/A |
Continuous Operation | 60 minutes @ 100% rating | IEEE C57.91 |
Cooling System | ONAN (Oil Natural Air Natural) | IEEE C57.12.00 |
Dimensions | Ø250mm × 4500mm (H) Base: 1800mm | N/A |
Weight | <500kg | N/A |
Dual-Function Capabilities
Precision Voltage Measurement
2000:1 nominal dividing ratio
≤±1.5% measurement accuracy
Dedicated HV output to voltmeter
Partial Discharge Detection
Specialized PD tester connection
≤2pC sensitivity at 400kV
Simultaneous measurement capability
Premium Performance Features
Ultra-Low Partial Discharge
≤5pC at 500kV (100% rated voltage)
≤2pC at 400kV (80% rated voltage)
Detects microscopic insulation defects
Exceptional Thermal Stability
<5 ppm/°C temperature coefficient
ONAN cooling maintains precision
Consistent performance in varying environments
Dual-Output Design
Independent HV measurement output
Dedicated PD detection connection
Simultaneous operation capability
Advanced Engineering Design
Optimized Form Factor
Ø250mm × 4500mm compact profile
Base footprint: 1800mm
Weight: <500kg for easier handling
Specialized Connection System
Dual isolated output connectors
HV measurement to voltmeter
Direct PD tester connection
Thermal Management
ONAN cooling efficiency
Maintains <0.5% dielectric loss
60-minute continuous operation
Performance Validation
Test Parameter | Requirement | Result |
---|---|---|
Partial Discharge @ 400kV | ≤5pC | ≤2pC |
Temperature Stability | <10 ppm/°C | <5 ppm/°C |
Continuous Operation | 30 minutes | 60 minutes stable |
Dielectric Loss @ 20°C | <0.5% | 0.42% average |
Testing conducted per IEC 60270 and IEEE 4 standards
Critical Applications
Transformer PD Diagnostics
Simultaneous voltage measurement and partial discharge detection
Cable Insulation Testing
Identify microscopic flaws with ≤2pC sensitivity
High-Voltage Research
Precision measurement for dielectric studies
Quality Assurance
Critical component validation in manufacturing
Compliance & Certifications
IEC 60060-1: High-voltage test techniques
IEEE 4: Standard for HV testing
IEC 60270: Partial discharge measurements
IEC 61869-11: Coupling capacitors
CE, RoHS, and UKCA certified
Safety Compliance: Meets IEEE 516-2022 safety requirements for 500kV installations