>400kV Range
LQHDR 500kV/2.5kΩ/2A Damping Resistor: Advanced Solution for High-Power Testing
Engineering Overview
The LQHDR 500kV/2.5kΩ/2A damping resistor delivers exceptional performance in high-voltage test environments requiring precise power handling and ultra-low partial discharge. Designed for demanding applications in transformer testing, impulse generators, and HVDC systems, this resistor combines robust thermal management with industry-leading electrical characteristics.
Technical Specifications
Parameter | Specification | Standard |
---|---|---|
Rated Voltage | 500 kV AC | IEC 60060-1 |
Nominal Resistance | 2.5 kΩ ±1% | IEEE Std 62 |
Rated Current | 2 A | IEC 60115-8 |
Rated Power | 10 kW | IEC 60269 |
Frequency Range | 50/60/100/120 Hz | IEC 60038 |
Partial Discharge | <3 pC @ 500 kV | IEC 60270 |
Operating Duration | 60 min @ 100% load | ANSI/NETA MTS-2019 |
Surface Temp Rise | <100 K continuous | IEC 60505 |
Core Performance Features
Multi-Frequency Capability
Engineered for global applications with optimized performance at:
Standard power frequencies (50/60Hz)
Enhanced testing ranges (100/120Hz)
Constant resistance tolerance (±0.5%) across all frequencies
Thermal Management System
Advanced cooling fins maintain <100K temperature rise
Ceramic-encased resistive elements for heat distribution
Derating-free operation at 10kW for 60-minute intervals
Partial Discharge Control
The <3pC PD rating at 500kV ensures:
Accurate measurements in sensitive transformer tests
Elimination of electromagnetic interference (EMI)
Prevention of insulation degradation
Design Innovations
Electrical Construction
Non-inductive bifilar winding technique
Graded capacitance shielding rings
Corona-resistant silicone coatings
Mechanical Durability
Stainless steel structural framework
UV-resistant polymer housings
Vibration-damping mounting system
Critical Applications
Transformer Testing Systems
Induced voltage tests (IVT) at 100-120Hz
Partial discharge measurement circuits
Lightning impulse wavefront control
Specialized Test Environments
HVDC valve commissioning
Gas-insulated substation (GIS) diagnostics
Cable factory acceptance testing
Operational Guidelines
Installation Requirements
Minimum clearance: 4.2 meters (500kV applications)
Vertical mounting for optimal convection cooling
Ambient humidity: <70% non-condensing
Maintenance Protocol
Infrared thermography before/after 10kW operations
Bi-annual resistance verification (±1% tolerance)
Annual PD measurement validation
Performance Comparison
Feature | Standard Resistors | LQHDR 500kV |
---|---|---|
Power Density | 7-8 kW | 10 kW |
Frequency Flexibility | 50/60Hz only | 50-120Hz full range |
Cooling Recovery | 2-3 hours | 60 minutes |
Why This Resistor?
Industry-leading 10kW power handling at 500kV
Unique multi-frequency capability (50-120Hz)
Certified <3pC partial discharge performance
Robust thermal design for <100K temperature rise
Conclusion
The LQHDR 500kV/2.5kΩ/2A damping resistor sets new benchmarks for high-voltage testing equipment with its unprecedented 10kW power rating, multi-frequency operation, and ultra-low partial discharge characteristics. Its optimized thermal management and strict compliance with IEC/IEEE standards make it indispensable for utilities, testing laboratories, and manufacturers requiring maximum reliability in extreme electrical environments.