400kV ~ 600kV Range
LQHVF 500kV/1000pF Multi-Frequency Capacitor Voltage Divider & Coupling Capacitor
Premium dual-function solution offering exceptional performance across multiple frequencies (50/60/100/120Hz) with industry-leading ≤3pC partial discharge at full 500kV operation.
Multi-Frequency Operation: Only 500kV solution supporting 50Hz, 60Hz, 100Hz and 120Hz - ideal for global power systems testing
Technical Specifications
Parameter | Specification | Test Standard |
---|---|---|
Rated Voltage | 500kV | IEC 60060-1 |
Rated Capacity | 1000pF | IEEE 4 |
Supported Frequencies | 50Hz, 60Hz, 100Hz, 120Hz | IEC 60076 |
Partial Discharge | ≤3pC @ 100% rated voltage | IEC 60270 |
Dielectric Loss | <0.2% | IEC 60422 |
Measuring Accuracy | ≤±1% | IEEE 112 |
Dividing Ratio | 2000:1 | N/A |
Continuous Operation | 60 minutes @ 100% rating | IEEE C57.91 |
Insulation Withstand | 550kV (110% rated) for 1min | IEC 60071 |
Cooling System | ONAN (Oil Natural Air Natural) | IEEE C57.12.00 |
Multi-Frequency Performance
50/60Hz Power Systems
Optimized for global power grids
±0.8% accuracy at 50/60Hz
Ideal for utility applications
100/120Hz Applications
Aviation and military power systems
±0.9% accuracy at 100/120Hz
Critical for specialized equipment
Cross-Frequency Stability
Consistent performance across range
Unified calibration for all frequencies
No reconfiguration required
Advanced Performance Features
Ultra-Low Partial Discharge
≤3pC at 500kV (100% rated voltage)
Industry-leading sensitivity
Detects microscopic insulation defects
Precision Measurement
±1% voltage accuracy
2000:1 nominal dividing ratio
Stable across all frequencies
Robust Insulation
550kV withstand capability
Zero abnormal discharge during testing
Advanced dielectric fluid system
Dual-Function Capabilities
Precision Voltage Divider
2000:1 dividing ratio
Multi-frequency measurement
±1% accuracy guarantee
Coupling Capacitor
1000pF capacity
Power line carrier communication
Signal injection capability
Simultaneous operation supported for integrated monitoring systems
Frequency Performance Validation
Frequency | Accuracy | Dielectric Loss | PD Level |
---|---|---|---|
50Hz | ±0.78% | 0.18% | ≤3pC |
60Hz | ±0.75% | 0.17% | ≤3pC |
100Hz | ±0.85% | 0.19% | ≤3pC |
120Hz | ±0.92% | 0.20% | ≤3pC |
Tested at 500kV per IEEE 4 and IEC 60270 standards
Global Applications
International Power Utilities
50/60Hz compatibility for global grid testing
Aerospace Power Systems
400Hz compatibility for aircraft equipment
Industrial Machinery
100/120Hz testing for specialized equipment
Research Laboratories
Multi-frequency testing capability
Compliance & Certifications
IEC 60060-1: High-voltage test techniques
IEEE 4: Standard for HV testing
IEC 60270: Partial discharge measurements
IEC 61869-11: Coupling capacitors
MIL-STD-704: Aircraft power characteristics
CE, RoHS, UKCA, and FAA certified
Safety Compliance: Meets IEEE 516-2022 safety requirements for 500kV installations