400kV ~ 600kV Range
LQHVF-400kV/500pF Oil-Immersed Voltage Divider
Precision 60Hz measurement solution with 2000:1 ratio, LT 0.2% dielectric loss, and modular removable design for high-voltage applications
Technical Specifications
Parameter | Specification | Testing Standard |
---|---|---|
Rated Voltage | 400kV AC (60Hz) | IEC 60060-1 |
Nominal Capacitance | 500pF ±3% | IEC 60358 |
Dividing Ratio | 2000:1 | - |
Dielectric Loss (tanδ) | <0.2% | IEC 60247 |
Measuring Accuracy | ≤±1% | IEC 60060-2 |
Continuous Operation | 60 min @ 400kV | IEC 61180 |
Cooling System | ONAN (Oil Natural Air Natural) | IEC 60296 |
Frequency | 60Hz (50Hz optional) | IEC 60060-1 |
Modular Structural Design
Removable Oil-Immersed Components
HV Arm Assembly
400kV-rated capacitor section
Mineral oil-impregnated dielectric
Vacuum-processed insulation
LV Measurement Arm
Precision voltage sensing circuit
Shielded output terminals
Temperature-compensated design
Corona Ring System
Aluminum alloy construction
Optimized diameter for 400kV operation
Quick-disconnect assembly
Removable Base
Stabilizing platform with leveling feet
Integrated grounding terminals
Transport locking mechanism
Performance Advantages
Precision Measurement
2000:1 ratio with ≤±1% accuracy
Phase displacement <0.1° at 60Hz
Bandwidth: DC - 1kHz
Low-temperature drift: 0.005%/°C
Thermal Management
ONAN cooling system
ΔT <5°C during 60-min operation
Operating range: -30°C to +55°C
Sealed oil preservation system
Operational Safety
Automatic discharge circuit (τ <60s)
Dual-pressure relief mechanisms
Oil level/temperature monitoring
NFPA 70E compliant grounding
Certified Performance Validation
Testing Protocol Compliance
Dielectric loss <0.2% verified at 60Hz (IEC 60247)
Ratio accuracy ≤±1% from 10% to 100% rated voltage
60-minute thermal stability test at 400kV
Impulse withstand: 480kV (1.2/50μs wave)
Partial discharge <5pC at 400kV
IEC 60270 IEC 60060-1 IEC 60060-2 ANSI C37.90
Industrial Applications
Power Transmission
400kV+ substation equipment testing
Circuit breaker diagnostics
Busbar insulation verification
High-Power Laboratories
Transformer impulse testing
GIS partial discharge mapping
Cable system commissioning
Renewable Energy
Offshore wind farm converters
Solar inverter testing
BESS (Battery Storage) validation