400kV ~ 600kV Range
LQHVF 400kV/4000pF Capacitive Voltage Divider
High-capacity solution for extended duration high-voltage testing with industry-leading thermal stability and measurement accuracy.
Extended Operation: Only 400kV divider certified for 60-minute continuous operation at full 400kV/4000pF capacity
Technical Specifications
Parameter | Specification | Test Standard |
---|---|---|
Rated Voltage | 400kV | IEC 60060-1 |
Rated Capacity | 4000pF | IEEE 4 |
Operation Frequency | 50Hz | IEC 60076 |
Partial Discharge | ≤10pC @ 100% rated voltage | IEC 60270 |
Dielectric Loss | <0.2% | IEC 60422 |
Measuring Accuracy | ≤±1% | IEEE 112 |
Dividing Ratio | 2000:1 | N/A |
Continuous Operation | 60 minutes @ 100% rating | IEEE C57.91 |
Insulation Withstand | 440kV for 1min (110% rated) | IEC 60071 |
Cooling System | ONAN (Oil Natural Air Natural) | IEEE C57.12.00 |
High-Capacity Performance Features
Extended Operation Capability
Certified 60-minute operation at 400kV/4000pF
Ideal for long-duration acceptance tests
50% longer runtime than standard dividers
Precision Measurement
±1% voltage accuracy
2000:1 nominal dividing ratio
Optimized for 50Hz power systems
Advanced Thermal Management
ONAN cooling maintains stable operation
<0.2% dielectric loss at 20°C
Natural convection eliminates fans
Robust Engineering Design
Transport-Optimized Corona Control
Aerospace-grade aluminum corona rings
Segmented design for easy packing
Corona-free HV connections
Stable Removable Pedestal
Engineered for seismic stability
Quick-assembly field deployment
Integrated measurement ports
Flexible Measurement Options
Special lead-wire to VF power sources
Single/two-stage serial measurement
Scalable corona-free connections
Performance Validation
Test | Duration | Result |
---|---|---|
Continuous Operation @ 400kV | 60 minutes | Stable ±0.8% accuracy |
Dielectric Loss @ 20°C | Continuous monitoring | 0.18% average |
440kV Withstand Test | 1 minute | No discharge (passed) |
Thermal Stability | 60-min operation cycle | Max ΔT = 15°C |
Testing conducted per IEC 60270 and IEEE 4 standards
Industry Applications
Transformer Long-Duration Testing
60-minute induced voltage tests with continuous monitoring
Cable Manufacturing QA
Extended partial discharge measurements during production
Generator Acceptance Testing
Sustained high-voltage validation for turbine generators
Research & Development
Material testing under prolonged high-voltage stress
Compliance & Certifications
IEC 60060-1: High-voltage test techniques
IEEE 4: Standard for HV testing
IEC 60270: Partial discharge measurements
ANSI/NETA ATS-2021: Acceptance testing
CE, RoHS, and UKCA certified
Safety Compliance: Meets IEEE 516-2022 safety requirements for 400kV installations