400kV ~ 600kV Range
LQHVF 400kV/3000pF Capacitive Voltage Divider & Coupling Capacitor
Dual-function solution combining precision voltage measurement and power line coupling capabilities with industry-leading ≤2pC partial discharge performance.
Industry First: Only 400kV device achieving ≤2pC PD at full load while functioning as both measurement divider and coupling capacitor
Technical Specifications
Parameter | Specification | Test Standard |
---|---|---|
Rated Voltage | 400kV | IEC 60060-1 |
Rated Capacity | 3000pF | IEEE 4 |
Operation Frequency | 60Hz | ANSI C68.3 |
Partial Discharge (100% voltage) | ≤2pC | IEC 60270 |
Partial Discharge (80% voltage) | ≤3pC | |
Dielectric Loss @ 20°C | <0.2% | IEC 60422 |
Measuring Accuracy | ≤±1% | IEEE 112 |
Dividing Ratio | 2000:1 | N/A |
Insulation Withstand | 440kV for 1min (110% rated) | IEC 60071 |
Cooling System | ONAN (Oil Natural Air Natural) | IEEE C57.12.00 |
Dual-Function Capabilities
Precision Voltage Divider
2000:1 nominal dividing ratio
≤±1% measurement accuracy
Single and two-stage serial measurement
Coupling Capacitor
3000pF capacity for power line coupling
60Hz optimized performance
Signal injection for PD monitoring
Advanced Performance Features
Ultra-Low Partial Discharge
≤2pC at 400kV (100% rated voltage)
≤3pC at 320kV (80% rated voltage)
Detects microscopic insulation defects
Thermal Stability
ONAN cooling maintains dielectric properties
<0.2% dielectric loss at 20°C
Natural convection eliminates moving parts
Robust Insulation System
440kV/1min withstand capability
Zero abnormal discharge during testing
Advanced dielectric fluid formulation
Engineering Design Excellence
Optimized Corona Control
Aerospace-grade aluminum corona rings
Segmented design for transportation
Corona-free HV connections
Removable Stability Pedestal
Engineered for seismic stability
Quick-assembly field deployment
Integrated measurement ports
Measurement Flexibility
Special lead-wire to VF power sources
Single/two-stage serial measurement
Scalable corona-free connections
Performance Validation Testing
Test Parameter | Requirement | Actual Result |
---|---|---|
Partial Discharge @ 400kV | ≤5pC | ≤2pC |
Partial Discharge @ 320kV | ≤5pC | ≤3pC |
440kV Withstand Test | No discharge | Passed (0 discharges) |
Dielectric Loss @ 20°C | <0.2% | 0.15% average |
Testing conducted per IEC 60270 and IEEE 4 standards
Industry Applications
Power Line Carrier Communication
3000pF coupling capacity for signal injection in HV transmission lines
Transformer PD Monitoring
Simultaneous voltage measurement and PD detection during tests
Cable Quality Assurance
Identify insulation flaws with ≤2pC sensitivity at 400kV
Substation Commissioning
Dual-function operation reduces equipment requirements by 40%
Compliance & Certifications
IEC 60060-1: High-voltage test techniques
IEEE 4: Standard for HV testing
IEC 60270: Partial discharge measurements
ANSI/NETA ATS-2021: Acceptance testing
CE, RoHS, and UKCA certified
Safety Note: Complies with IEEE 516-2022 safety requirements for 400kV live working distances