High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

400kV ~ 600kV Range

LQHVF 400kV/3000pF Dual-Function Capacitive Divider & Coupling Capacitor | ≤2pC Partial Discharge

Advanced 400kV capacitive divider/coupling capacitor with ≤2pC PD, ±1% accuracy & 440kV withstand. ONAN cooling, 2000:1 ratio. Ideal for HV systems.


  • US$ 10,155.00
  • Lead time: 30days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHVF 400kV/3000pF Capacitive Voltage Divider & Coupling Capacitor

Dual-function solution combining precision voltage measurement and power line coupling capabilities with industry-leading ≤2pC partial discharge performance.

Industry First: Only 400kV device achieving ≤2pC PD at full load while functioning as both measurement divider and coupling capacitor

Technical Specifications

ParameterSpecificationTest Standard
Rated Voltage400kVIEC 60060-1
Rated Capacity3000pFIEEE 4
Operation Frequency60HzANSI C68.3
Partial Discharge (100% voltage)≤2pCIEC 60270
Partial Discharge (80% voltage)≤3pC
Dielectric Loss @ 20°C<0.2%IEC 60422
Measuring Accuracy≤±1%IEEE 112
Dividing Ratio2000:1N/A
Insulation Withstand440kV for 1min (110% rated)IEC 60071
Cooling SystemONAN (Oil Natural Air Natural)IEEE C57.12.00

Dual-Function Capabilities

Precision Voltage Divider

  • 2000:1 nominal dividing ratio

  • ≤±1% measurement accuracy

  • Single and two-stage serial measurement

Coupling Capacitor

  • 3000pF capacity for power line coupling

  • 60Hz optimized performance

  • Signal injection for PD monitoring

Advanced Performance Features

Ultra-Low Partial Discharge

  • ≤2pC at 400kV (100% rated voltage)

  • ≤3pC at 320kV (80% rated voltage)

  • Detects microscopic insulation defects

Thermal Stability

  • ONAN cooling maintains dielectric properties

  • <0.2% dielectric loss at 20°C

  • Natural convection eliminates moving parts

Robust Insulation System

  • 440kV/1min withstand capability

  • Zero abnormal discharge during testing

  • Advanced dielectric fluid formulation

Engineering Design Excellence

Optimized Corona Control

  • Aerospace-grade aluminum corona rings

  • Segmented design for transportation

  • Corona-free HV connections

Removable Stability Pedestal

  • Engineered for seismic stability

  • Quick-assembly field deployment

  • Integrated measurement ports

Measurement Flexibility

  • Special lead-wire to VF power sources

  • Single/two-stage serial measurement

  • Scalable corona-free connections

Performance Validation Testing

Test ParameterRequirementActual Result
Partial Discharge @ 400kV≤5pC≤2pC
Partial Discharge @ 320kV≤5pC≤3pC
440kV Withstand TestNo dischargePassed (0 discharges)
Dielectric Loss @ 20°C<0.2%0.15% average

Testing conducted per IEC 60270 and IEEE 4 standards

Industry Applications

Power Line Carrier Communication

3000pF coupling capacity for signal injection in HV transmission lines

Transformer PD Monitoring

Simultaneous voltage measurement and PD detection during tests

Cable Quality Assurance

Identify insulation flaws with ≤2pC sensitivity at 400kV

Substation Commissioning

Dual-function operation reduces equipment requirements by 40%

Compliance & Certifications

  • IEC 60060-1: High-voltage test techniques

  • IEEE 4: Standard for HV testing

  • IEC 60270: Partial discharge measurements

  • ANSI/NETA ATS-2021: Acceptance testing

  • CE, RoHS, and UKCA certified

Safety Note: Complies with IEEE 516-2022 safety requirements for 400kV live working distances