<100kV Range
LQHVF 36kV/1000pF Coupling Capacitor & Capacitive Voltage Divider
Scalable HV System: Single-stage and dual-stage configurations for flexible voltage measurement up to 72kV
Advanced HV Instrument for Industrial Power Systems
Engineered for 36kV applications, the LQHVF combines precision measurement with exceptional flexibility. The 1000pF capacitance and scalable design enable:
Standard 36kV measurements in single-stage configuration
Extended 72kV capability in dual-stage series connection
Precise voltage division with ≤±1% accuracy
Sensitive partial discharge detection (<5pC)
Technical Specifications
Parameter | Specification | Performance Advantage |
---|---|---|
Rated Voltage | 36kV | Industrial power system compatibility |
Withstand Voltage | 40kV | 10% safety margin beyond rating |
Capacitance | 1000pF | Optimal signal coupling for PD detection |
Voltage Ratio | 1000:1 | 36V output at 36kV input |
Partial Discharge | <5pC @ 36kV | Meets IEC 60270 Class I requirements |
Dielectric Loss | <0.5% | Superior insulation efficiency |
Dimensions | p100/p180×520mm | Dual-base options for stability |
Weight | ≈15kg | Portable for field applications |
Operating Time | 60min @ 36kV | Full-power diagnostic capability |
Scalable Measurement Configurations
Single-Stage Operation
Voltage Range: Up to 36kV
Connection: Direct HV corona-free terminal
Measurement: Via special lead-wire to variable frequency source
Setup Time: <5 minutes
Dual-Stage Series Connection
Voltage Range: Up to 72kV
Configuration: Cascaded HV arms
Measurement: Differential measurement technique
Extended Capacity: +100%
HV Connection: Corona-free terminals with scalable interfaces prevent RF interference during measurements.
Innovative Structural Design
Removable Aluminum Corona Rings
High-strength alloy optimized for transport
40% lighter than steel alternatives
Dual-Base System
p100/p180 options for surface adaptability
Stability on uneven terrain
Modular Construction
Quick-disconnect HV arm, V arm, and base
Field assembly in 8 minutes
ONAN Cooling
Natural oil/air convection system
Thermal stability during operation
Measurement System Features
Special Measuring Lead-Wire: Shielded connection to variable frequency power source
Corona-Free HV Connection: Special electrode geometry eliminates surface discharge
Scalable Interface: Standardized connectors for series configuration
Automatic Discharge: Integrated 500kΩ bleeder resistors
Compliance & Applications
Standards Compliance: IEC 60270:2000, IEEE 4-2013, EN 60060-1:2010
Key Applications:
Factory testing of 36kV switchgear and transformers
On-line PD monitoring in industrial substations
Extended voltage testing up to 72kV
Power quality analysis in renewable energy systems
High-voltage research laboratories
Operational Protocol
Single-Stage Setup
Select appropriate base (p100/p180)
Assemble components
Connect measuring lead to VF source
Apply HV via corona-free terminal
Dual-Stage Setup
Connect two units in series
Synchronize measurement systems
Use differential measurement technique
Apply HV across the series chain
Pro Tip: For dual-stage operation, use IRIG-B time synchronization between measurement devices for phase-accurate readings
Transport & Handling Advantages
Removable Corona Rings: Reduce package size by 35%
Lightweight Design: 15kg total weight with carrying handles
Protected Connectors: Dust caps for all interfaces
Crush-Resistant Packaging: Custom foam inserts for components
Field Benefit: 50% faster deployment than fixed-structure dividers
Why This System Stands Out
Measurement Flexibility
Single/Dual-stage configurations
Transport Optimization
Removable aluminum components
Safety Assurance
40kV withstand voltage rating
Precision
≤±1% accuracy at 50Hz