<150kV Range
LQHDR Series 20kV/5kΩ/1A High-Power Protecting Resistor
Robust Protection for High-Voltage Systems
The LQHDR protecting resistor delivers 5kW power handling at 20kV/1A with industrial-grade durability. Featuring nickel-chromium wire wound on an epoxy pipe and ≤80K temperature rise, it provides critical protection for:
Transformer divider circuits
High-voltage test equipment
Power transmission monitoring systems
Impulse voltage generators
Technical Specifications
Parameter | Specification | Standard |
---|---|---|
Model | LQHDR | - |
Rated Voltage | 20 kV AC/DC | IEC 60137 |
Nominal Resistance | 5 kΩ ±2% | IEC 60255 |
Rated Current | 1 A continuous | IEC 60076 |
Power Rating | 5 kW | IEC 60076-14 |
Partial Discharge (PD) | Meets system test standards | IEC 60270 |
Operating Cycle | 1 hour ON / 1 hour OFF (4 cycles/day) | IEC 60076-14 |
Temperature Rise | ≤80K at full load | IEC 60076-2 |
Dimensions | Ø150 × 450mm | - |
Weight | <30 kg | - |
Terminals | Flange connections (M16) | IEC 61238-1 |
Robust Construction
Epoxy Pipe Core Design
Nickel-chromium resistance wire precision-wound on high-grade epoxy pipe provides:
Dielectric strength >30kV/mm
Thermal stability up to 200°C
Mechanical vibration resistance
⌀150mm
↓
450mm
Divider Connection System
Integrated connecting tubes enable direct mounting to transformer dividers with:
HV bushing compatibility
Thermal expansion compensation
Corrosion-resistant flanges
Cyclic Operation Capability
Industrial Duty Cycle
Designed for 4 daily cycles of 1-hour full-power operation (20kV/1A) followed by 1-hour cooldown period.
Thermal Management
Optimized airflow design maintains surface temperature rise ≤80K during continuous operation at 100% load:
Axial cooling fins
6m/s natural convection rating
Thermal cut-off at 150°C
Industrial Applications
Transformer Divider Protection
Prevents voltage transients in measurement dividers during:
Lightning impulse tests
Switching surge measurements
DC withstand voltage tests
HV Test Equipment
Provides current limiting and damping in:
Cable fault locators
Circuit breaker test sets
Insulation resistance testers
Installation Requirements
Mounting: Horizontal position with 300mm clearance
Connections: 35mm² cables with M16 compression lugs
Environment: Indoor (IP54) or outdoor with canopy
Safety: Grounding strap connection mandatory