High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

<100kV Range

LQHVF 10kV/300pF Capacitive Voltage Divider & Coupling Capacitor - Precision HV Measurement

High-precision LQHVF 10kV/300pF capacitive voltage divider with <5pC partial discharge, ≤1% accuracy & ONAN cooling. Ideal for critical HV measurements.


  • US$ 982.00
  • Lead time: 30 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHVF 10kV/300pF Capacitive Voltage Divider & Coupling Capacitor

Ultra-Low Partial Discharge Design: <5pC at Rated Voltage for Critical HV Applications

Dual-Function Precision Instrument

The LQHVF series serves as both a high-accuracy voltage divider and signal coupling capacitor, engineered for 10kV power systems. With 100:1 ratio and ≤1% accuracy, it enables:

  • Partial discharge (PD) monitoring in transformers and switchgear

  • Harmonic analysis in modern power grids

  • Calibration of protection relays per IEC 60255

  • Dielectric loss tangent measurements

Technical Specifications

ParameterSpecificationPerformance Advantage
Rated Voltage10kVIndustrial-grade HV capability
Capacitance300pFMinimal circuit interference
Voltage Ratio100:1Direct compatibility with measurement devices
Partial Discharge (PD)<5pC @ 10kVExceeds IEC 60270 Class II requirements
Dielectric Loss<0.5%Superior insulation performance
Cooling SystemONAN (Oil Natural Air Natural)Maintains thermal stability during extended operation
Operating Time60min @ 10kV
Continuous @ 8kV
Flexible for diagnostic & monitoring applications

Innovative Structural Design

Patented Modular Architecture: Enables field maintenance without oil replacement

  • Oil-Immersed Construction: Mineral oil insulation enhances thermal dissipation and arc resistance

  • Removable Corona Rings: Optimized geometry reduces surface gradients

  • Tri-Component System: L-arm, HV arm, and base allow component-level servicing

  • Compact Dimensions: 65mm × 90mm × 420mm (fits confined substation spaces)

Critical Applications

Industry Insight: 300pF capacitance provides optimal balance for PD detection and power frequency measurement

  1. Partial Discharge Monitoring: Detect insulation weaknesses in cables and GIS

  2. Power Quality Analysis: Measure harmonics up to 5kHz bandwidth

  3. Protective Relay Testing: Generate precise reference signals

  4. Research & Development: Characterize dielectric materials under HV stress

Compliance & Safety

Engineered to global standards for HV equipment:

  • IEC 61869-11:2023 (Instrument Transformers)

  • IEEE C57.13-2016 (Accuracy Classes)

  • EN 50191 (Installation Requirements)

  • CAT IV 600V safety rating

Safety Feature: Integrated pressure-relief diaphragm prevents oil leakage during faults.

Operational Protocol

  1. Pre-Use Check: Verify oil level in sight glass before energization

  2. Grounding: Connect base to earth ground with ≥6mm² cable

  3. Cooling: Maintain 0.5m clearance for air circulation

  4. Calibration: Perform biannual dielectric loss tests per IEEE 4-2013

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message

Leave Your Message