Cable and line Testing Instrument
LQHV-545 Arrester Discharge Counter Validation System
Dual-Function Counter Calibration
This 8/20μs surge generator verifies both lightning strike counting and leakage current monitoring functions of modern arresters. Generates 100A+ impulses for field validation per IEC 60099-5 standards.
Technical Parameters
Input voltage | AC220V±10% 50Hz; DC12V |
Impulse voltage | 0-1600V Precision:2%±5V (Customized higher voltages as required) |
Impulse current | >100A (8/20μS square wave) |
Calibration current | 0-10mA, ±2%±3 words |
Instrument power consumption | <30VA |
Diemension | 320×240×150mm3 |
Core Technologies
1. Dual-Valve Surge Generation
Precise 8/20μs waveform shaping
±5% current amplitude stability
100+ consecutive surges without degradation
2. Smart Leakage Monitoring
Real-time μA-level current measurement
Auto-baseline compensation
Trend analysis for early MOA degradation
Field Calibration Process
Connect to arrester counter terminals
Select surge current level (20-100A)
Verify counter increments
Monitor leakage current stability
Typical Applications
Substation Maintenance: Annual counter verification
Tower Arresters: Post-lightning strike checks
MOA Condition: Leakage current baseline recording
Safety Protections
Interlocked test leads
Visible discharge indicator
30-minute auto power-off
Why Choose LQHV-545?
Traditional Methods
Require separate impulse generator
No leakage current verification
Bulky equipment
LQHV-545 Advantages
All-in-one field solution
Dual-function validation
Backpack-portable design