Cable and line Testing Instrument
LQHV-540 Zinc Oxide Arrester Diagnostic System
Precision MOA Condition Assessment
This live-line capable tester analyzes resistive leakage current with 0.1μA resolution to detect ZnO block aging/moisture per DL474.5-92 standards. Combines Fourier analysis with magnetic isolation for substation-grade accuracy.
Technical Parameters
Reference voltage input range (peak) | 10V ~ 200V, can be customized (0-250V) |
Full leakage current Measuring range (peak) | 100uA ~ 8mA, can be customized (0-20mA) |
Resistive current Measuring range (peak) | 100uA ~ 8mA, can be customized (0-20mA) |
Capacitive current Measuring range (peak) | 100uA ~ 8mA, can be customized (0-20mA) |
Angle Measuring range | 0°~90° |
Power | 4W |
System measurement accuracy | ± (reading × 5% + 5 words) (harmonic current is not more than 2 mA) |
AC power supply | AC220V ±10%,50Hz ±1% |
Advanced Diagnostic Features
1. Harmonic Current Separation
Fundamental wave extraction (50/60Hz)
3rd/5th harmonic distortion analysis
Capacitive current compensation
2. Field-Adaptive Technology
Edge phase correction (±1° adjust)
Auto-PT ratio matching
Noise rejection >60dB
Test Workflow
Connect to MOA ground lead
Reference PT secondary voltage
Auto-calculate resistive current (Ir)
Evaluate harmonic content
Data Management
500+ test records with timestamps
Micro-print reports on-site
USB export for trending analysis
Typical Fault Detection
Aging ZnO Blocks
↑ Resistive current + ↑ 3rd harmonics
Moisture Ingress
↑ Fundamental wave distortion
Valve Degradation
Abnormal phase-angle shifts
Standards Compliance
DL/T 474.5-2018 (Field testing)
IEC 60099-5 (MOA standards)
GB/T 191-2008 (Packaging)