≤800kV Range
LQHIVG 600KV-7.5KJ Impulse Voltage Generator | High-Efficiency Testing System
Optimized High-Voltage Testing Platform
The LQHIVG 600KV-7.5KJ delivers exceptional efficiency in lightning impulse testing. With 85% voltage utilization at <1000pF loads and a 6-stage modular design, this generator provides precision dielectric validation for power transformers, switchgear, and transmission equipment with ≤1.0% voltage instability.
Global Standards Compliance
Certified for international high-voltage testing protocols:
IEC 60060-1/2-2010: Test definitions & measurement systems
IEC 61083-1/2: Digital measurement requirements
ANSI/IEEE 4a-2001: High-voltage techniques
ASTM D2484/D2518: Insulation testing standards
Core Technical Specifications
Parameter | Specification |
---|---|
Rated Voltage | ±600kV |
Stage Configuration | 6 stages |
Rated Energy | 7.5kJ |
Stage Voltage | ±100kV |
Stage Capacitance | 0.25μF |
Impulse Capacity | 0.04167μF |
Lightning Impulse Performance
Standard Waveform (300-2000pF load)
Front time (T1): 1.2μs ±30%
Tail time (T2): 50μs ±20%
Peak deviation: ≤3%
Chopping Wave Capability
Adjustable chopping time: 2-5μs
Peak deviation: ≤3%
Voltage Utilization Efficiency
Load Capacitance | Lightning Wave Efficiency |
---|---|
<1000pF | ≥85% |
<2000pF | ≥80% |
Control System & Reliability
Feature | Performance |
---|---|
Synchronization Range | 20-100% rated voltage (±20% polarity sync) |
Firing Out-of-Control Rate | <5% |
Voltage Instability | <±1.0% |
Minimum Output Voltage | ≥20% rated voltage |
Operational Efficiency
Cycling Performance
High-voltage mode (>66% rated voltage): 90s charge/discharge cycles
Standard mode (<66% rated voltage): 45s charge/discharge cycles
Industrial Applications
EHV transformer impulse withstand testing (IEC 60076)
Gas-insulated substation (GIS) commissioning
High-voltage cable system validation
Power utility equipment certification
Safety & Calibration
Annual calibration per IEC 61083-2 requirements
IEEE 4a safety margin enforcement
ASTM D2518 dielectric verification
Remote operation capability for >300kV tests
Performance Validation
System verification includes:
NIST-traceable voltage calibration
High-speed oscilloscopic waveform analysis
Load-specific efficiency testing (300-2000pF range)