High Voltage Test Solutions
Persistently developing technology, improving quality, management, and service standards

≤800kV Range

LQHIVG 600KV-7.5KJ Impulse Voltage Generator | High-Efficiency Testing System

600KV-7.5KJ Impulse Voltage Generator with 85% voltage utilization. Features 6-stage design, ≤3% peak deviation, and IEC/IEEE compliance for precision high-voltage testing.


  • US$ 17,817.00
  • Lead time: 60 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHIVG 600KV-7.5KJ Impulse Voltage Generator | High-Efficiency Testing System

Optimized High-Voltage Testing Platform

The LQHIVG 600KV-7.5KJ delivers exceptional efficiency in lightning impulse testing. With 85% voltage utilization at <1000pF loads and a 6-stage modular design, this generator provides precision dielectric validation for power transformers, switchgear, and transmission equipment with ≤1.0% voltage instability.

Global Standards Compliance

Certified for international high-voltage testing protocols:

  • IEC 60060-1/2-2010: Test definitions & measurement systems

  • IEC 61083-1/2: Digital measurement requirements

  • ANSI/IEEE 4a-2001: High-voltage techniques

  • ASTM D2484/D2518: Insulation testing standards

Core Technical Specifications

ParameterSpecification
Rated Voltage±600kV
Stage Configuration6 stages
Rated Energy7.5kJ
Stage Voltage±100kV
Stage Capacitance0.25μF
Impulse Capacity0.04167μF

Lightning Impulse Performance

Standard Waveform (300-2000pF load)

  • Front time (T1): 1.2μs ±30%

  • Tail time (T2): 50μs ±20%

  • Peak deviation: ≤3%

Chopping Wave Capability

  • Adjustable chopping time: 2-5μs

  • Peak deviation: ≤3%

Voltage Utilization Efficiency

Load CapacitanceLightning Wave Efficiency
<1000pF≥85%
<2000pF≥80%

Control System & Reliability

FeaturePerformance
Synchronization Range20-100% rated voltage (±20% polarity sync)
Firing Out-of-Control Rate<5%
Voltage Instability<±1.0%
Minimum Output Voltage≥20% rated voltage

Operational Efficiency

Cycling Performance

  • High-voltage mode (>66% rated voltage): 90s charge/discharge cycles

  • Standard mode (<66% rated voltage): 45s charge/discharge cycles

Industrial Applications

  • EHV transformer impulse withstand testing (IEC 60076)

  • Gas-insulated substation (GIS) commissioning

  • High-voltage cable system validation

  • Power utility equipment certification

Safety & Calibration

  1. Annual calibration per IEC 61083-2 requirements

  2. IEEE 4a safety margin enforcement

  3. ASTM D2518 dielectric verification

  4. Remote operation capability for >300kV tests

Performance Validation

System verification includes:

  • NIST-traceable voltage calibration

  • High-speed oscilloscopic waveform analysis

  • Load-specific efficiency testing (300-2000pF range)

>>>WhatsApp Communication<<<

>>>Click To Get Quote<<<

Leave Your Message