LQHIVG 600KV-5KJ Impulse Voltage Generator | Dual-Waveform High-Voltage Testing

600KV-5KJ Impulse Voltage Generator with lightning/switching impulse capabilities. Features 6-stage design, ≤1% voltage instability, and IEC/IEEE compliance for high-voltage testing.


  • US$ 16,394.00
  • Lead time: 60 days

>>>WhatsApp Communication<<<

Product Details

Product Tags

LQHIVG 600KV-5KJ Impulse Voltage Generator | Dual-Waveform High-Voltage Testing

Advanced Dual-Impulse Testing Platform

The LQHIVG 600KV-5KJ Impulse Voltage Generator delivers precision lightning and switching impulse tests up to 600kV. Featuring a 6-stage modular design with 900kV/7.5kJ upgrade capability, this system validates insulation performance in power transformers, GIS equipment, and transmission infrastructure with ±1.0% voltage stability.

International Standards Compliance

Certified for global high-voltage testing protocols:

  • IEC 60060-1/2-2010: Test techniques & measurement systems

  • IEC 61083-1/2: Digital measurement requirements

  • ANSI/IEEE 4a-2001: High-voltage testing methods

  • GB311/GB16927: Chinese national standards

  • ASTM D2484/D2518: Insulation testing

Technical Specifications

ParameterSpecification
Rated Voltage±600kV (Upgradeable to ±900kV)
Stage Configuration6 stages
Rated Energy5kJ (7.5kJ at 900kV)
Stage Voltage±100kV
Stage Capacitor0.166μF/100kV
Stage Energy0.833kJ

Impulse Waveform Performance

Lightning Impulse (1.2/50μs)

  • Front time: 1.2μs ±30%

  • Tail time: 50μs ±20%

  • Amplitude tolerance: ±3%

  • Peak oscillation: <5%

  • Efficiency: ≥90% (no test object)

Switching Impulse (250/2500μs)

  • Front time: 250μs ±20%

  • Tail time: 2500μs ±60%

  • Efficiency: ≥75% (3000pF test object)

Control System & Reliability

FeaturePerformance
Synchronous Range10-100% rated voltage (±20% polarity sync)
Discharge Control<2% out-of-control rate
Voltage Instability<±1.0%
Sparking Range10-100% Un
Minimum Output≥10% rated voltage

Operational Efficiency

Cycling Performance

  • High-voltage mode (>70% rated voltage): 120s charge/discharge cycles

  • Standard mode (

    <70% rated="" voltage="">
  • Minimum discharge time: ≥60s at max voltage

Industrial Applications

  • Extra-high-voltage (EHV) transformer testing

  • Gas-insulated switchgear (GIS) validation

  • Transmission line insulation coordination

  • Renewable energy grid interconnection tests

Safety & Calibration

  1. Annual IEC 61083-2 compliant calibration

  2. IEEE 4a safety margin enforcement

  3. Dielectric verification per ASTM D2518

  4. Remote operation capability for >300kV tests

Performance Validation

All waveforms comply with IEC 60060-1 and GB311 standards. System verification includes:

  • NIST-traceable voltage calibration

  • High-speed oscilloscopic waveform analysis

  • Temperature/humidity compensated measurements