<1000kV Range
LQHID 600KV-300pF Weak Damping Capacitor Voltage Divider: Technical Specifications
Advanced Design Features
The LQHID 600KV-300pF features an innovative weak damping capacitive design with MWF600 impulse capacitors and multistage distributed damping resistors. Its non-inductive structure ensures accurate waveform measurement, while the polyurethane housing provides superior protection and mobility.
MWF600 Impulse Capacitor: High-performance core component for stable 600kV operation
Multistage Damping Resistors: Precisely distributed for optimal waveform control
Non-Inductive Construction: Parallel-connected low-voltage arm capacitors eliminate measurement distortion
Durable Polyurethane Housing: Lightweight yet robust protection with integrated corona covers
Technical Specifications
Parameter | Specification |
---|---|
Rated Voltage | +600kV |
HV Arm Capacitance | 300pF |
Voltage Ratio | 2000:1 |
Partial Response Time (Tas) | ≤100nS |
Over-Impulse Limit (β) | ≤20% |
Scale Factor Uncertainty (Kg) | ≤±1% |
Construction Height | Approx. 2.1m (with corona covers) |
Mobility | Movable polyurethane design |
Performance Advantages
Ultra-Fast Response: ≤100ns response time captures lightning impulse transients with precision
Exceptional Accuracy: ≤±1% scale factor uncertainty for reliable measurements
Superior Waveform Fidelity: Non-inductive design preserves signal integrity up to 600kV
Rugged Construction: Polyurethane housing withstands harsh field conditions
Standards Compliance
Fully compliant with international and Chinese standards:
GB/T 311.1: Insulation coordination standards
GB/T 16927: High-voltage test techniques
IEC 60060-1: High-voltage test procedures
Square wave response meets all GB/T requirements
Typical Applications
Lightning impulse testing of power transformers
On-site commissioning of 600kV-class equipment
High-voltage laboratory calibration
Transient overvoltage research
Switchgear impulse withstand verification
Operational Recommendations
Maintain minimum 3m clearance during 600kV operation
Use matched impedance coaxial cables (≤5m length recommended)
Perform quarterly dielectric tests on HV capacitors
Inspect corona covers before each high-voltage test
Store in controlled environment (10°C-30°C, humidity ≤70%)