Damping Resistor
HGDR 750kV/5kΩ/0.5A Gas Insulated Damping Resistor
Designed for ultra-high-voltage energy dissipation, the HGDR 750kV/5kΩ/0.5A combines 750kV dielectric strength with precision 5kΩ resistance in a compact SF6-insulated package. This industrial-grade resistor delivers reliable performance in impulse testing, HVDC research, and high-energy physics applications.
Technical Specifications
Parameter | Specification |
---|---|
Rated Voltage | 750kV DC/AC peak |
Nominal Resistance | 5kΩ ±5% |
Rated Current | 0.5A continuous |
Power Rating | 1.875kW |
Frequency | 50Hz |
Short-Circuit Duration | 20 minutes at full rating |
Temperature Rise | ≤80K at 100% load |
Insulation Medium | SF6 Gas (0.55MPa) |
Key Features
1. Extreme Voltage Performance
750kV rating with 825kV withstand capability
SF6 gas insulation prevents corona discharge
Graded ring electrodes for uniform field distribution
2. Precision Energy Absorption
5kΩ ±5% tolerance for consistent measurements
Low thermal drift (<250ppm/°C)
1.875kW power dissipation capacity
3. Robust Thermal Management
≤80K temperature rise at full load
20-minute continuous operation at 0.5A
Stainless steel enclosure with forced convection
Construction Details
Resistive Element
Nickel-chromium alloy wire winding
Alumina ceramic core substrate
Electrostatic shielding layers
Gas System
0.55MPa SF6 gas pressure
Double-sealed maintenance-free design
Integrated pressure relief valve
Typical Applications
800kV+ transmission line testing
HVDC converter station commissioning
Pulsed power system development
High-voltage capacitor bank testing
Performance Advantages
High Energy Density: 2.25kJ pulse absorption per cycle
Controlled Heating: ≤80K rise ensures stable resistance
Safety Assurance: Pressure-activated disconnect
Long Service Life: 10+ years maintenance-free operation
Installation Guidelines
Electrical Requirements
750kV-rated silicone rubber bushings
Minimum 3m clearance to ground
Equalizing rings recommended above 500kV
Operational Protocol
Maximum 20-minute continuous operation
60-minute cooldown between cycles
Annual SF6 pressure checks required
Compliance Standards
IEC 60060-1 (High-voltage testing)
IEEE Std 4 (HV measurement techniques)