HET 750kVA Variable Frequency Exciter Transformer Technical Specifications
1. Electrical Parameters
Parameter | Specification |
---|---|
Rated Capacity | 750kVA |
Frequency Range | 25-400Hz (Rated at 25Hz) |
Impedance | ≤5% |
Acoustic Noise | ≤60dB |
1.1 High Voltage Winding
Voltage Tap | Current Rating |
---|---|
4.2kV | 178.5A |
3.6kV | |
2.5kV | |
1.75kV |
1.2 Low Voltage Winding
Voltage Options: 2×450V / 2×500V / 2×550V
Current Rating: 2×750A
2. Thermal Management
Component | Temperature Limit |
---|---|
Winding | ≤65K rise |
Oil Surface | ≤55K rise |
Cooling Method: ONAN (Oil Natural Air Natural)
Insulation Oil: Grade A, 25# transformer oil
Continuous Operation: 60 minutes at full load
3. Core Construction
3.1 Magnetic Core
Shell-type oil-immersed design
Core Material: D0130-30 high-grade silicon steel
Low Bm value for reduced eddy current losses
3.2 Winding Configuration
Independent HV winding design
Double-coil construction with copper conductors
Electrostatic shielding between windings
Built-in measuring coil for HV voltage monitoring
4. Safety Features
Clearance Design: Prevents partial discharge/corona
Oil Monitoring:
Expansion tank with moisture absorber
Oil temperature thermograph
Visual oil level indicator
Transport Safety: Component layout optimized for shipping
5. Performance Guarantees
Stable output across 25-400Hz range
No measurable corona at rated voltage
≤5pC partial discharge at 4.2kV
6. Compliance Standards
IEC 60076-1 (Power Transformers)
IEEE C57.12.00 (General Requirements)
EN 50588-1 (Mobile Test Equipment)