HET 500kVA Exciter Transformer Technical Specifications & Safety Features
1. Core Technical Parameters
Parameter | Specification |
---|---|
Rated Capacity | 500kVA |
Rated Frequency | 50Hz |
Phase Configuration | Single Phase |
Cooling Method | ONAN (Oil Natural Air Natural) |
Input Voltage | 10kV |
Output Voltage | 13.7kV/60kV (tap voltage, water termination test) |
Impedance Voltage | <6% |
2. Current Ratings
Input Current: 50A
HV Output Current: 36.6A (13.7kV tap) / 4A (60kV tap)
3. Advanced Protection Systems
3.1 Electrostatic Shielding
Specialized shielding between HV windings features:
Dedicated electrostatic shield layer
Voltage distribution optimization
Partial discharge reduction
3.2 Surge Protection
Zinc oxide arresters on all ground connections
Piezoresistors installed per HV output
Breakdown protection for both operator and equipment
4. Insulation System Design
4.1 Multi-Layer Protection
Cylinder-type winding configuration
Inter-turn insulation layers
Compound insulation tube skeleton
4.2 Voltage Distribution Control
Engineering solutions include:
Balanced top/bottom winding area design
Electrostatic shield compensation
Iron core electromagnetic shielding
5. Operational Considerations
Test Conditions: Requires water termination for 60kV testing
Maintenance: Regular oil analysis recommended for ONAN systems
Safety Compliance: Meets IEC 60076 power transformer standards
This exciter transformer is specifically engineered for high-voltage testing applications where precise voltage regulation and robust safety protection are critical requirements.